Study on Auto-DR and Pre-cooling of Commercial Buildings with Thermal Mass in California
نویسندگان
چکیده
This paper discusses how to optimize pre-cooling strategies for buildings in a hot California climate zone with the Demand Response Quick Assessment Tool (DRQAT), a building energy simulation tool. This paper outlines the procedure used to develop and calibrate DRQAT simulation models, and applies this procedure to eleven field test buildings. The results of a comparison between the measured demand savings during the peak period and the savings predicted by the simulation model indicate that the predicted demand shed match well with measured data for the corresponding Auto-Demand Response (Auto-DR) days. The study shows that the accuracy of the simulation models is greatly improved after calibrating the initial models with measured data. These improved models can be used to predict load reductions for automated demand response events. The simulation results were compared with field test data to confirm the actual effect of demand response strategies. Results indicate that the optimal demand response strategies worked well for most of the buildings tested in this hot climate zone.
منابع مشابه
IRANIAN VERNACULAR ARCHITECTURE: NOTABLE EXAMPLE OF A THERMAL MASS
In some climates, massive buildings made of stone, masonry, concrete, earth and … can be utilized as one of the simplest and most effective ways of reducing building heating and cooling loads. Very often such savings could be achieved in the design stage of the building and with a relatively low-cost. Such declines in building envelope heat losses combined with optimized material configurati...
متن کاملLoad Control Using Building Thermal Mass
This paper provides an overview of research related to use of building thermal mass for shifting and reducing peak cooling loads in commercial buildings. The paper presents background on the concept and the problem of optimizing zone temperature setpoints and provides specific results that have been obtained through simulations, controlled laboratory testing, and field studies. The studies have...
متن کاملVentilated hollow core slab as a thermal mass strategy and its effect on thermal comfort; (case study: lotion college, England)
Thermal mass is the material's ability to store heat and release it after an amount of time and concrete is considered one of the best thermal mass material. Since concrete has been used widely in many building constructions, by considering the capability of concrete in terms of thermal mass, it is worthwhile to use this ability of concrete in order to build buildings more healthy and comfortab...
متن کاملPassive Energy Air-to-Water Heat Pipe Based Heat Exchanger and its Potential of Air Pre-cooling in Air Conditioning Systems for Iran Climate
Air pre-cooling equipment is normally being employed in air-conditioning systems for pre-cooling the ambient outdoor air to enhance the air-conditioning systems performance. In this study, the potential of a passive water-to-air heat pipe based heat exchanger (HPHEX) for air pre-cooling purpose in air-conditioning systems for the high cooling load demanding regions of Iran was investigated. To ...
متن کاملTowards Lean Buildings - Examples and Experience from a German Demonstration Program for Energy Efficiency and Solar Energy Use in Commercial Buildings
The paper presents the description and initial evaluation of a number of commercial large scale buildings situated across Germany. The study has been carried out within the framework of the demonstration program SolarBau, which has been initiated and funded by the German Ministry of Economy and Technology. The program funds up to 25 demonstration buildings and their collective evaluation. Fundi...