Fast Energy Loss Computation and Fuzzy-Based Shunt Capacitor Insertion
نویسندگان
چکیده
Fast energy loss computation is implemented using supervisory control and data acquisition system (SCADA) with personal computer. Logic Control Array (LCA) and EPROM circuits are used to implement SCADA system and to measure the VoltAmpere, KVolt and KVAR and draw the daily load curve for residential and commercial customers. LCA, EPROM and PC are used to simplify the electronic circuits, reduce the cost and speed up the computation time. An illustrative example was done to measure, store and show the active power, reactive power, load voltage, load current, power factor, and the shunt capacitors current. It is found that when 2.7 MVAR bank capacitor is inserted in the network the load current is decreased from 740.8A to 688.4A and the power factor is improved from 80% up to 93%, and led to add more loads on the network and release the feeder capacitor. A rule-based fuzzy decision maker has been designed and tested with the real data collected from Jordan using SCADA system. The calculated output is almost similar to that obtained from the first approach presented in this paper. The advantage of using fuzzy decision maker is its simplicity that can be implemented on a programmable logic device and can be programmed to improve the power factor.
منابع مشابه
Reduction in the Transient Time of Shunt Active Filters Using Intelligent Controllers
This paper deals with the implementation of new proposed strategy for the reduction in the transient time of shunt active filter using intelligent controllers. Intelligent control is a class of control techniques that use various AI computing approaches like fuzzy logic, neural network, evolutionary computation, genetic algorithm etc. The proposed strategy works on the principle of energy of th...
متن کاملA new method based on fuzzy system and gravitational optimal detector for capacitor placement, considering nonlinear loads
This paper describes an advantageous method for using the capacitor banks in the distribution network, optimally. The aim is to determine the count, location and capacitor values in order to minimize the annual cost resulting from energy losses and capacitor bank’s installation cost. Besides, in the case of having nonlinear loads in the network, by installing capacitors in appropriate locations...
متن کاملA Novel Control Strategy for Enhancement of Power Quality Using Fuzzy Logic
This paper deals with simulation of shunt active filters using fuzzy logic to improve the power quality and reduction in the transient time of capacitor voltage, when there is change in load. Shunt active power filter can compensate current harmonics by injecting equal-but-opposite harmonic compensating current .A new control strategy is proposed which is based on energy of the capacitor, dc-li...
متن کاملFuzzy Control for Shunt Capacitors Applied in Distribution Feeders
The lack of reactive energy flow control in distribution networks causes an increase of electrical losses and problems with the voltage profile. The main objective of this work is to develop a fuzzy control system for automatic capacitor banks applied to distribution feeders, which was focused on the improvement of the equipment performance allowing a better correction of the system reactive an...
متن کاملA Hybrid Algorithm for Optimal Location and Sizing of Capacitors in the presence of Different Load Models in Distribution Network
In practical situations, distribution network loads are the mixtures of residential, industrial, and commercial types. This paper presents a hybrid optimization algorithm for the optimal placement of shunt capacitor banks in radial distribution networks in the presence of different voltage-dependent load models. The algorithm is based on the combination of Genetic Algorithm (GA) and Binary Part...