A field investigation of passive radiative cooling under Hong Kong’s climate
نویسندگان
چکیده
This paper discusses the feasibility of cooling using radiation under Hong Kong’s hot and humid climate. Three different designs of a passive radiative cooler were studied in this work. The three designs include non-vacuum, and vacuum with seven potassium chloride (KCl) IR-Pass windows as well as one system with a single KCl IR-Pass window. The coolers were examined during daytime and night time operation as well as under different sky conditions, such as clear, cloudy and partly cloudy. Investigation was mainly based on the temperature difference between the radiative cooler and ambient air. The experimental results showed that the passive radiative cooler with seven KCl windows and the cooler design without vacuum provided a satisfactory cooling effect at night (i.e. the ambient air temperature was reduced by about 6e7 C), but the coolers could not produce a cooling effect during daytime under any of Hong Kong’s weather conditions. The same results were obtained for the passive radiative cooler with the single KCl window during daytime operation. However, the cooling capacity of the passive radiative cooler design without vacuum under a clear night sky achieved 38 W/m2. © 2017 Elsevier Ltd. All rights reserved.
منابع مشابه
Investigation of Radiative Cooling Using a Photonic Composite Material for Water Harvesting
The objective of this study is to design and analyse materials which are capable of harvesting water from thin air using condensation phenomenon which employs the radiative cooling approach. These passive cooling materials not only solve the water generating problems, but also employed in various cooling applications. The fundamental concept of radiative cooling is analysed and the performance ...
متن کاملHeat Transfer Study of Convective-Radiative Fin under the influence of Magnetic Field using Legendre Wavelet Collocation Method
The development and production of high performance equipment necessitate the use of passive cooling technology. In this paper, heat transfer study of convective-radiative straight fin with temperature-dependent thermal conductivity under the influence of magnetic field is carried out using Legendre wavelet collocation method. The numerical solution is used to investigate the effects of magnetic...
متن کاملPassive Energy Air-to-Water Heat Pipe Based Heat Exchanger and its Potential of Air Pre-cooling in Air Conditioning Systems for Iran Climate
Air pre-cooling equipment is normally being employed in air-conditioning systems for pre-cooling the ambient outdoor air to enhance the air-conditioning systems performance. In this study, the potential of a passive water-to-air heat pipe based heat exchanger (HPHEX) for air pre-cooling purpose in air-conditioning systems for the high cooling load demanding regions of Iran was investigated. To ...
متن کاملRadiative Cooling: Principles, Progress, and Potentials
The recent progress on radiative cooling reveals its potential for applications in highly efficient passive cooling. This approach utilizes the maximized emission of infrared thermal radiation through the atmospheric window for releasing heat and minimized absorption of incoming atmospheric radiation. These simultaneous processes can lead to a device temperature substantially below the ambient ...
متن کاملRadiative cooling for concentrating photovoltaic systems
Radiative cooling, a unique and uncommon passive cooling method for devices operating outdoors, has recently been demonstrated to be effective for photovoltaic thermal management. In this work, we investigate the effect of radiative cooling as a complement to existing passive cooling methods like convective cooling in a related system with much higher heat loads: a high-concentration photovolta...
متن کامل