Identification of Various Internal Faults of Transformer Based on No-load Current Analysis

نویسندگان

  • Rushi R. Desai
  • Amit N. Patel
  • Vinod R. Gupta
چکیده

The internal faults of transformer can be identified by various techniques. The proposed technique is by the analysis of no-load current and harmonic contents present in it. The no-load current of transformer is non-sinusoidal for sinusoidal input voltage. And hence it contains harmonics in healthy condition of transformer. But if transformer has any internal fault then the no-load current magnitude and its harmonic content will vary depending upon the type of fault. The winding fault increases the %THDi and magnitude of noload current, whereas the core fault increases only the %THDi of no-load current. For winding fault if the inter-turn fault is on the primary side then both %THDi and magnitude of noload current increases but if the inter-turn fault is on secondary side then only magnitude of no-load current will increase. Keywords—Transformer Internal Faults, %THDi, No-load current analysis, Harmonics.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Artificial Intelligence Based Approach for Identification of Current Transformer Saturation from Faults in Power Transformers

Protection systems have vital role in network reliability in short circuit mode and proper operating for relays. Current transformer often in transient and saturation under short circuit mode causes mal-operation of relays which will have undesirable effects. Therefore, proper and quick identification of Current transformer saturation is so important. In this paper, an Artificial Neural Network...

متن کامل

Protection Scheme of Power Transformer Based on Time–Frequency Analysis and KSIR-SSVM

The aim of this paper is to extend a hybrid protection plan for Power Transformer (PT) based on MRA-KSIR-SSVM. This paper offers a new scheme for protection of power transformers to distinguish internal faults from inrush currents. Some significant characteristics of differential currents in the real PT operating circumstances are extracted. In this paper, Multi Resolution Analysis (MRA) is use...

متن کامل

تشخیص بین جریان خطای داخلی و جریان هجومی در ترانسفورماتور با استفاده از روش آشوب

In this paper, a new method has been presented for differential protection of power transformers.  In this approach, chaotic method has been used for distinguishing of inrush current from internal fault current of the transformer. The proposed algorithm has been designed based on analysis of harmonic components of the differential current of the transformer due to internal faults and inrus...

متن کامل

Designing of a New Transformer Ground Differential Relay Based on Probabilistic Neural Network

Low- impedance transformer ground differential relay is a part of power transformer protection system that is employed for detecting the internal earth faults. This is a fast and sensitive relay, but during some external faults and inrush current conditions, may be exposed to maloperation due to current transformer (CT) saturation. In this paper, a new intelligent transformer ground differentia...

متن کامل

Power Auto-transformer Mechanical Faults Diagnosis ‎Using Finite Element based FRA

Frequency response analysis (FRA) is a sensitive ‎method established for testing the mechanical integrity of ‎transformers. However, interpretation of FRA signature still ‎needs expert opinions and there is no FRA interpretation code ‎generally accepted. Various mechanical faults with different ‎extents on power transformers are required to aid FRA ‎interpretation. To address this challenge, in...