Active noise control in a one dimensional acoustic duct, in which fluid medium inside the duct has a mean flow velocity, is studied. The acoustic duct model with general boundary conditions is solved in Laplace domain and infinite dimensional system transfer functions are obtained. For controller designs, appropriate microphone, and noise canceling source locations are determined. Low order finite dimensional transfer function approximations of actual system transfer functions are obtained. It is found that, in a selected frequency range, approximations represent actual system in a satisfactory way. By using approximated system transfer functions, finite dimensional, low order, optimal H2 and H1 controllers are synthesized via linear matrix inequalities method. Closed loop frequency response and time domain simulations show that the controllers successfully suppress unwanted sound, which propagates along the duct. [DOI: 10.1115/1.4026410]
منابع مشابه
Control of Nozzle Flow Using Microjets at Supersonic Mach Regime
This article reports the active control of base flows using the experimental procedure. Active control of base pressure helps in reducing the base drag in aerodynamic devices having suddenly expanded flows. Active control in the form of microjets having 0.5 mm radius placed at forty-five degrees apart is employed to control the base pressure. The Mach numbers of the present analysis are 1.7, 2....
متن کامل3D Simulation of the Effects of the Plasma Actuator on the Unsteady, Turbulent and Developing Flow within a Circular Duct
The objective of current paper is 3D simulation of turbulent, developing flow and unsteady within a circular duct in presence of the body force vector persuaded by Dielectric barrier discharge (DBD) plasma actuator inside the surface of geometry for the first time. This article aims at investigating of applying plasma actuator to control separation with special arrangement of electrodes. For th...
متن کاملActive noise control of an acoustic duct using feedback control
Forced air cooling systems, such as an airconditioning system produce noise. For a pleasant living environment, this noise is undesirable. A way to suppress produced noise is reducing the sound in the duct where the air flows through afterwards. a his report handles the noise reduction in an active duct silencer by the use of a discrete feedback controller. Models of the involved processes are ...
متن کاملA Robust Feedforward Active Noise Control System with a Variable Step-Size FxLMS Algorithm: Designing a New Online Secondary Path Modelling Method
Several approaches have been introduced in literature for active noise control (ANC)systems. Since Filtered-x-Least Mean Square (FxLMS) algorithm appears to be the best choice as acontroller filter. Researchers tend to improve performance of ANC systems by enhancing andmodifying this algorithm. This paper proposes a new version of FxLMS algorithm. In many ANCapplications an online secondary pat...
متن کاملExperimental Investigations of Different Microphone Installations for Active Noise Control in Ducts
A request on ventilation systems today is the feature of a low noise level. A common method to attenuate ventilation noise is to use passive silencers. However, such silencers are not suitable for the lowest frequencies and one solution is to use active noise control (ANC) to increase the noise attenuation in the low frequency range. Normally when using a feedforward ANC system to attenuate duc...