Comparison and Analysis of On-line Partial Discharge Measurement Methods for Gas Insulation Substation
نویسندگان
چکیده
In this paper, we compare and analyze the signals of acoustic emission (AE) sensor, high-frequency current transformer (HF-CT) and capacitive coupled (CC) sensor inspection methods when they are used to detect the partial discharge (PD) in gas isolation substations (GIS). The PD location feasibility of the AE method is also studied. In general, the leakage currents are measured by using the HF-CT. And the electric fields are measured by using the CC sensors. However, the PD signals measured from the electric methods are usually hard to judge their accurate location while the AE method has good direction ability. Since the frequency of PD signals from AE measurements is usually less than 100 kHz, within the specific location, we can use AE sensors with frequency response range from 23 ~ 80 kHz to do the on-site, long-term observation. From the practically measured results, we definitely obtained the PD signals in a 161-kV GIS for all three different sensors.
منابع مشابه
Sensitivity Assessment of Lightning Protection Device Aging Effect on Distribution Substation Insulation
Insufficient electrical endurance of equipment and insulation failure against overvoltage is one of the most effective reasons for failure the power line. Lightening, switching or other disruptive parameters can cause line outage or distribution substation failure. There are different devices used to improve the safety, reliability, and power quality of the system. Surge arresters are one of t...
متن کاملAdvancements in Partial Discharge Analysis to Diagnose Stator Winding Problems
On-line partial discharge (PD) testing has been used for over 50 years to assess the condition of motor and generator stator winding insulation systems. In the past decade, advanced hardware and software have enabled superior methods of converting the PD data into practical information about the relative condition of the insulation, as well as determining the root causes of any insulation deter...
متن کاملPartial Discharge in High Voltage Insulating Materials
High voltage transmission has been chosen in electric power system due to its capability to transfer a large amount of electric power. Several key equipments such as generator, transformer, GIS, cable and insulator play important role in determining the reliability of the power system. The high voltage equipments in general contain gas, liquid or solid insulation. Defects and a particular condi...
متن کاملApplication of HFCT and UHF Sensors in On-Line Partial Discharge Measurements for Insulation Diagnosis of High Voltage Equipment
Partial discharge (PD) measurements provide valuable information for assessing the condition of high voltage (HV) insulation systems, contributing to their quality assurance. Different PD measuring techniques have been developed in the last years specially designed to perform on-line measurements. Non-conventional PD methods operating in high frequency bands are usually used when this type of t...
متن کاملPartial Discharge Theory, Modeling and Applications To Electrical Machines
Partial discharge monitoring is an effective on-line predictive maintenance test for motors and generators, as well as other electrical distribution equipment. The benefits of on-line testing allow for equipment analysis and diagnostics during normal production. Corrective actions can be planned and implemented, resulting in reduced unscheduled downtime. This paper will present a theory to prom...
متن کامل