Analysis of Full and Chopped Lightning Impulse Voltages from Transformer Tests Using the New K-factor Approach
نویسندگان
چکیده
The analysis of the lightning impulses is made graphical according to IEC 60060-1: 1989. A new algorithm has been proposed to analyse the parameters, front time, time to half, peak value, of full and chopped lightning impulses. The algorithm provides a procedure for obtaining the parameters of the impulse voltages from waveforms with varying degrees of distortions in the front part of the impulse. Oscillations or overshoot in the peak region of the impulse are such distortions. The new algorithm was tested in different laboratories with different program languages and the results were compared to the IEC 60060-1: 1989 evaluation. Investigations with the new k-factor approach are already made with 52 TDG test data but the scientific view of real test data is missing. Therefore, full and chopped lightning impulses of transformer tests from manufacturers were investigated with the global and the residual filtering methods and were compared to the IEC 60060-1: 1989 evaluation.
منابع مشابه
Analysis of the Voltage Stresses on Transformer Windings under Different Type of Surges
Standard high voltage lightning and switching impulse tests are performed on Extra High Voltage (EHV) transformers during manufacture to ascertain the breakdown strength of insulation used. But during their service, transformers encounter numerous voltage transients of complex and varying wave shapes which do not necessarily resemble these standard surge type voltages. This paper reports the re...
متن کاملEffect of the overshoot level in an alternative method for processing of tail chopped lightning impulses
The construction of new Ultra High Voltage laboratories requires more studies about standards for equipment as well as for testing and measurement techniques. Currently, the analysis of tail chopped lightning impulse waveforms is possible only by prior application of a full reference lightning impulse, creating difficulties for testing and processing of waveforms. A new method for evaluating th...
متن کاملTransient Voltage Distribution in Transformer Winding (experimental Investigation)
Abstract In this work, the non-liner voltage distribution in transformer winding is investigated that occurs due switching and lightning. Transformer winding is modeled in the alternative transients program (ATP) version of Electromagnetic transients program (EMTPRV). EMTP software is used to simulate the very fast transient overvoltage. An experimental setup that consist of , Recurrent surge g...
متن کاملHigh Frequency Transformer Isolated Quasi Z-Source Cascade Multilevel Inverter
In this paper, a new structure of HFTI-qZS-CMI has been proposed. The proposed structure is capable of generating high-voltage for medium to high power applications. By adding a switch, a capacitor and a high-frequency transformer and also eliminating an inductor from each qZS-CMI cell, the HFTI-qZS-CMI structure will be created. Using the high-frequency transformer in the proposed structure, l...
متن کاملCharacterisation and Generation of High Impulse Voltages and Currents
Transmission and distribution of electrical energy involves the application of highvoltage apparatus like power transformers, switchgear, overvoltage arrestors, insulators, power cables, transformers, etc., which are exposed to high transient voltages and currents due to internal and external overvoltages. Before commissioning, they are therefore tested for reliability with standard impulse vol...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
عنوان ژورنال:
دوره شماره
صفحات -