Averaging level control in the presence of frequent inlet flow upsets
نویسنده
چکیده
Buffer tanks are widely used within the process industry to prevent flow variations from being directly propagated throughout a plant. The capacity of the tank is used to smoothly transfer inlet flow upsets to the outlet. Ideally, the tank thus works as a low pass filter where the available tank capacity limits the achievable flow smoothing. For infrequently occurring upsets, where the system has time to reach steady state between flow changes, the averaging level control problem has been extensively studied. After an inlet flow change, flow filtering has traditionally been obtained by letting the tank level deviate from its nominal value while slowly adapting the outlet to cancel out the flow imbalance and eventually bringing back the level to its set-point. The system is then again in steady state and ready to surge the next upset. By ensuring that the single largest upset can be handled without violating the level constraints, satisfactory flow smoothing is obtained. In this thesis, the smoothing of frequently changing inlet flows is addressed. In this case, standard level controllers struggle to obtain acceptable flow smoothing since the system rarely is in steady state and flow upsets can thus not be treated as separate events. To obtain a control law that achieves optimal filtering while directly accounting for future upsets, the averaging level control problem was approached using robust model predictive control (MPC). The robust MPC differs in the way it obtains flow smoothing by not returning the tank level to a fixed set-point. Instead, it lets the steady state tank level depend on the current value of the inlet flow. This insight was then used to propose a linear control structure, designed to filter frequent upsets optimally. Analyses and simulation results indicate that the proposed linear and robust MPC controller obtain flow smoothing comparable to the standard optimal averaging level controllers for infrequent upsets while handling frequent upsets considerably better.
منابع مشابه
Performance Analysis of Robust Averaging Level Control
Frequent inlet flow changes, especially in the same direction, typically cause problems for averaging level controllers. To obtain optimal flow filtering while being robust towards future inlet flow upsets closed loop robust MPC has been used. It differs from other averaging controllers in that it does not return the tank level to a fixed set-point, but rather lets it depend on the current inle...
متن کاملPerformance Analysis of Robust Averaging Level Control, Report no. LiTH-ISY-R-3030
Frequent inlet flow changes, especially in the same direction, typically cause problems for averaging level controllers. To obtain optimal flow filtering while being robust towards future inlet flow upsets closed loop robust MPC was used. Its performance and robustness is analyzed and compared to the optimal averaging level controller. The knowledge gained from the robust MPC exercise is also u...
متن کاملPractical Control of Surge Tanks Suffering from Frequent Inlet Flow Upsets
In the presence of frequent inlet flow upsets, tuning of averaging level controllers is typically quite complicated since not only the size of the individual steps but also the time in between the subsequent steps need to considered. One structured way to achieve optimal filtering for such a case is to use Robust Model Predictive Control. The robust MPC controller is, however, quite computation...
متن کاملPractical Control of Surge Tanks Suffering from Frequent Inlet Flow Upsets, Report no. LiTH-ISY-R-3036
In the presence of frequent inlet flow upsets, tuning of averaging level controllers is typically quite complicated since not only the size of the individual steps but also the time in between the subsequent steps need to considered. One structured way to achieve optimal filtering for such a case is to use Robust Model Predictive Control. The robust MPC controller is, however, quite computation...
متن کاملRobust Averaging Level Control
Frequent inlet flow changes typically cause problems for averaging level controllers. For a frequently changing inlet flow the upsets do not occur when the system is in steady state and the tank level at its set-point. For this reason the tuning of the level controller gets quite complicated, since not only the size of the upsets but also the time in between them relative to the hold up of the ...
متن کامل