Seasonal Based Pollution Performance of 11kV and 33kV Silicon Composite Insulators
نویسندگان
چکیده
Abstract—This paper presents the experimental results of 11 kV and 33 kV silicon composite insulators under artificial salt and urea polluted conditions. The tests were carried out under different seasons like summer, winter, and monsoon. The artificial pollution is prepared by properly dissolving the salt and urea in the water. The prepared salt and urea pollutions are sprayed on the insulators and dried up for sufficiently large time. The process is continued until a uniform layer is formed on the surface of insulator. For each insulator rating, four samples were tested. The maximum leakage current and breakdown voltage were measured. From experimental data, performance of test specimen is evaluated by comparing breakdown voltage and leakage current during different seasons when exposed to salt and urea polluted conditions. From these results the performance of the insulators can be predicted when they are installed in industrial, agricultural, and coastal areas. The experimental tests were carried out in the High Voltage laboratory using two stage cascade transformer having the rating of 1000 kVA, 500 kV.
منابع مشابه
Improvement of Electrical Performance for Porcelain Insulators Using Silicone Rubber Coating
This work presents the effect of room temperature vulcanized (RTV) silicone rubber coating on cap and pin type porcelain insulator under ac (50Hz) flashover voltage (KV). Describes experimental results obtained for improvement of porcelain insulator removed from 33kV overhead transmission line at Aswan, Egypt after 28 years of service. Also, this study briefly surveys the environmental contamin...
متن کاملRisk assessment of desert pollution on composite high voltage insulators
Transmission lines located in the desert are subjected to desert climate, one of whose features is sandstorms. With long accumulation of sand and with the advent of moisture from rain, ambient humidity and dew, a conductive layer forms and the subsequent leakage current may lead to surface discharge, which may shorten the insulator life or lead to flashover thus interrupting the power supply. S...
متن کاملDesignation of an Indicator for flashover prediction of porcelain and glass insulators based on experimental tests.
Flashover of polluted insulators in contaminated areas is one of the most important factors influencing the operation of transmission and distribution lines and finally line outages. Therefore, it is essential to prevent and detect flashover in the insulators. Hence, utilizing the insulator status monitoring systems and predicting their functions have absorbed a lot of attention over the recent...
متن کاملAssessing Partial Discharge on Composite Insulators Under Desert Pollution Conditions
Transmission lines located in the Sinai desert are subjected to desert climate, one of whose features, especially in the spring, is sand storms. Line insulators are thus exposed to sand contamination, which may produce streamer discharges in the air surrounding insulator surface. Such discharges may lead to flashover. This paper examines the electric field and potential distributions on sand-po...
متن کاملPerformance Improvement of the Ceramic Outdoor Insulators Located at Highly Polluted Environment Using Room Temperature Vulcanized Silicone Rubber Coating
Ceramic insulators are widely used in transmission as well as in distribution lines. As outdoor insulators, the ceramic insulators are subjected to environmental stresses. In particular case, the insulators may severe high pollution exposure. Under the polluted condition, high leakage current will flow on the insulator surface and dry band arching may take place. The phenomena may initiate the ...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
عنوان ژورنال:
دوره شماره
صفحات -