A New Algorithm for Digital Low-Impedance Protection of Busbars GER-4000 A New Algorithm for Digital Low-Impedance Protection of Busbars
نویسندگان
چکیده
The paper presents a new algorithm, its implementation, and results of extensive testing, for a microprocessor-based lowimpedance busbar relay. For increased security, the presented technique combines percent differential and current directional protection principles. The directional (phase comparison) principle does not require a voltage signal as it responds to relative directions of the currents. For fast operation, the outlined approach uses an adaptive trip logic that shifts between the 2-of-of-2 operating mode and the differential principle alone depending on a detection of CT saturation. The saturation detector responds to a differential–restraint current trajectory and is capable of detecting saturation occurring as fast as approximately 2 msec into a fault. The presented solution is implemented as a centralized type microprocessor-based relay with a sub-cycle tripping time and exceptional immunity to CT saturation.
منابع مشابه
A Novel Algorithm for Digital Distance Relaying
Distance relays are used to protect EHV and HV Transmission lines. Over the past decades many algorithms have emerged for digital distance relays. These are based on the calculation of the transmission line impedance from the relaying to fault points. In this paper a novel method for digital distance relaying is proposed. In the method the tracking procedure is implemented. The method uses the ...
متن کاملA Novel Algorithm for Digital Distance Relaying
Distance relays are used to protect EHV and HV Transmission lines. Over the past decades many algorithms have emerged for digital distance relays. These are based on the calculation of the transmission line impedance from the relaying to fault points. In this paper a novel method for digital distance relaying is proposed. In the method the tracking procedure is implemented. The method uses the ...
متن کاملOptimal DG Allocation and Thyristor-FCL Controlled Impedance Sizing for Smart Distribution Systems Using Genetic Algorithm
Recently, smart grids have been considered as one of the vital elements in upgrading current power systems to a system with more reliability and efficiency. Distributed generation is necessary for most of these new networks. Indeed, in all cases that DGs are used in distribution systems, protection coordination failures may occur in multiple configurations of smart grids using DGs. In different...
متن کاملGrid Impedance Estimation Using Several Short-Term Low Power Signal Injections
In this paper, a signal processing method is proposed to estimate the low and high-frequency impedances of power systems using several short-term low power signal injections for a frequency range of 0-150 kHz. This frequency range is very important, and thusso it is considered in the analysis of power quality issues of smart grids. The impedance estimation is used in many power system applicati...
متن کاملCross Entropy-Based High-Impedance Fault Detection Algorithm for Distribution Networks
The low fault current of high-impedance faults (HIFs) is one of the main challenges for the protection of distribution networks. The inability of conventional overcurrent relays in detecting these faults results in electric arc continuity that it causes the fire hazard and electric shock and poses a serious threat to human life and network equipment. This paper presents an HIF detection algori...