Setting Considerations of Distance Relay for Transmission Line with STATCOM
نویسندگان
چکیده
Distance relay plays an important role in the protection of transmission lines. The application of flexible AC transmission systems (FACTS) devices, such as the static synchronous compensator (STATCOM), could affect the performance of the distance relay because of compensation effect. This paper analyzes the application of distance relay on the protection of a transmission line containing STATCOM. New setting principles for different protection zones are proposed based on this analysis. A typical 500 kV transmission system employing STATCOM is modeled using Matlab/Simulink. The impact of STATCOM on distance protection scheme is studied for different fault types, fault locations, and system configurations. Based on simulation results, the performance of distance relay is evaluated. The setting principle can be verified for the transmission line with STATCOM.
منابع مشابه
Impact Analysis of Midpoint Connected STATCOM on Distance Relay Performance
This paper presents the impact of the Static Synchronous Compensator (STATCOM) on the performance of distance protection of EHV transmission lines. A 400kV transmission system having midpoint connected STATCOM with its control circuit is modeled using MATLAB/SIMULINK software. The impact of STATCOM on distance relay for different fault conditions and different fault locations is analyzed. Simul...
متن کاملFault Location Method for STATCOM Connected Transmission Lines Using CCM
Determining the fault location using conventional impedance based distance relay in the presence of FACTS controllers is a challenging task in a transmission line. A new distance protection method is developed to locate the fault in a transmission line compensated with STATCOM with simple calculations. The proposed protection method considers the STATCOM injected/absorbed current to correct the...
متن کاملFault Analysis of Double Line Transmission System with STATCOM Controller Using Neuro-Wavelet Based Technique
The STATCOM (Synchronous Static Compensator) based on voltage source converter (VSC) is used for voltage regulation in transmission and distribution systems. The STATCOM can rapidly supply dynamic VARs required during system faults for voltage support. The apparent impedance is influenced by the reactive power injected or absorbed by the STATCOM, which will result in the under reaching or over ...
متن کاملImpedance-Based Out-of-Step Protection of Generator in the Presence of STATCOM
This paper presents a novel impedance-based approach for out-of-step (OOS) protection of a synchronous generator. The most popular and commonly used approaches for detecting OOS conditions are based on the measurement of positive sequence impedance at relay location. However, FACTS devices change the measured impedance value and thus disrupt the performance of impedance-based relay function. In...
متن کاملA new interval approach for setting the distance relay zones to achieve perfect selectivity and maximum sensitivity
In this paper, an interval approach is presented to achieve perfect selectivity and maximum sensitivity in distance relay zones, considering uncertainties. For this purpose, first, the uncertainties affecting the settings of the three zones of a distance relay are discussed. Then, by using the Monte-Carlo simulation, the uncertainties are modelled and the impedances seen by the distance relay a...