Transient Stability Analysis of an Industrial Cogeneration System
نویسندگان
چکیده
The purpose of the paper is to analyze the transient stability of an industrial cogeneration system in Hsin-Chu Science-Based Industrial Park using ETAP software. The cogeneration system is installed two 161kV/161kV high-impendence transformers with tap-changer to connect with TPC for decreasing the short-circuit fault current and increasing the fault critical clearing time. The transient stability of three types of operation modes in cogeneration units, 3G1S, 2G1S, and 1G1S, is analyzed. Under the 3G1S operation mode, the system frequency immediately restores to 60Hz after tie line tripping with the TPC. Under the 1G1S and 2G1S operation modes, the system frequency will continuously decrease after tie line tripping with the TPC. The system frequency must perform the load shedding to put back to 60Hz.
منابع مشابه
Protective Relay Setting of the Tie Line Tripping and Load Shedding for the Industrial Power System
This paper presents the proper underfrequency relay settings to enhance the operation of industrial power systems with cogeneration facilities. A cogeneration unit was installed in the plant in 1996 to supply the power demand of the plant. The cogeneration unit always faces the shutdown problem when a severe fault occurs on the nearby Taipower network. It is, therefore, necessary to investigate...
متن کاملAdaptive load shedding for an industrial petroleum cogeneration system
⇑ Corresponding author. E-mail addresses: [email protected] (C.-T. H (H.-J. Chuang), [email protected] (C.-S. Chen). This paper presents the design of adaptive load-shedding strategy by executing the artificial neural network (ANN) and transient stability analysis for an Industrial cogeneration facility. To prepare the training data set for ANN, the transient stability analysis has been p...
متن کاملLoad Shedding Design for an Industrial Cogeneration System
This paper presents transient stability analysis and enhancement of Industrial Cogeneration Plant (ICP) using Artificial Neural Network (ANN) based adaptive load shedding. By selecting the total in-plant generation, spinning reserve, total plant load and rate of change of frequency as the input neurons of the ANN, the minimum amount of load shedding is determined to maintain in-plant load-gener...
متن کاملPower System Transient Stability Analysis Based on the Development and Evaluation Methods
A novel method to compute the stability region in power system transient stability analysis is presented. This method is based on the set analysis. The key to this method is to construct the Hamilton-Jacobi-Isaacs (HJI) partial differential equation (PDE) of a nonlinear system, using which we can compute the backward reachable set by applying the level set methods. The backward reachable set of...
متن کاملSelection of Resistive and Inductive Superconductor Fault Current Limiters Location Considering System Transient Stability
Superconductor fault current limiter (SFCL) is an effective device to suppress high fault currents. This paper presents a comparative study of resistive and inductive fault current limiters from transient stability point of view. Appropriate location and type of the limiters in a HV substation is selected by a qualitative approach based on the equal area criterion. Study system is simulated by...
متن کامل