Voltage Stability in Wind Systems by Using Decoupled Statcom
نویسنده
چکیده
this paper presents a systematic approach based on eigenstructure assignment to determine the mode shape and transient response of a STATCOM utilized as an exciter for induction generators (IG). A physical control scheme, including four control loops: ac voltage, dc voltage, ac active current and ac reactive current controllers, is pre-specified for the STATCOM. A synthetic algorithm is proposed to embed these physical control loops in the output feedback path. With appropriate oscillation mode design (eigenstructure) in each state variable, the STATCOM active current and reactive current will no longer be governed by the same mode but driven by new respective modes. The simulation and experimental results demonstrated that under various system disturbances, the proposed mode decoupling STATCOM is effective in regulating IG terminal voltage. Keywords—Eigen structure assignment, induction generator (IG), static synchronous compensator (STATCOM), voltage sourced inverter (VSI).
منابع مشابه
Comparison of the effects of two flatness based control methods for STATCOM on improving stability in power systems including DFIG based wind farms
Power grids are complex, interconnected and nonlinear systems, and this will be more severe when they are subjected to high wind resources penetration. Static synchronous compensators (STATCOM) are used to improve voltage regulation and to meet grid codes in power systems, including doubly fed induction generators (DFIG) based wind farms. Despite the nonlinear nature of STATCOM, the conventiona...
متن کاملImproving the performance of wind turbine equipped with DFIG using STATCOM based on input-output feedback linearization controller
Using the FACTS controllers, such as static synchronous compensator (STATCOM), as it provides continuous reactive power, in the grid including wind turbine (WT) equipped with doubly fed induction generator, for improving voltage profile (under normal circumstances) and providing a transition ability from inductor generator transition state has been proposed. In this paper, in order to contr...
متن کاملImproving the performance of wind turbine equipped with DFIG using STATCOM based on input-output feedback linearization controller
Using the FACTS controllers, such as static synchronous compensator (STATCOM), as it provides continuous reactive power, in the grid including wind turbine (WT) equipped with doubly fed induction generator, for improving voltage profile (under normal circumstances) and providing a transition ability from inductor generator transition state has been proposed. In this paper, in order to contr...
متن کاملComparative Study of the Performance of Static Synchronous Compensator, Series Compensator and Compensator /Battery Integrated to a Fixed Wind Turbine (RESEARCH NOTE)
This paper studies the interest of the integration of battery energy storage with Static Synchronous Compensator (STATCOM) for improving the low voltage ride through capability (LVRT) of a fixed speed wind turbine connected to the grid. For this reason and by applying a grid fault, a comparison is made between integrating the SSSC, the STATCOM and the STATCOM with battery energy storage. The sy...
متن کاملPower quality improvement in DFIG system using D-STATCOM
The wind energy conversion system (WECS) differs from other power systems. It is clean and pollution free. But the output of wind power plant is fluctuated in nature. It depends on the wind speed. The nature of wind is variable. The variable wind generates fluctuated power. Fluctuated output is the major problem of wind power plant. This problem can be solved by using convertor units. The secon...
متن کامل