Mobile zoned/exponential LAF screen: a new concept in ultra-clean air technology for additional operating room ventilation.
نویسندگان
چکیده
A mobile screen (0.5 x 0.4 m) producing ultra-clean exponential LAF (air-flow central zone 0.6 m/s and peripheral zone 0.4 m/s) was investigated as an addition to conventional turbulent/mixing operating room ventilation. The evaluation was performed during strictly standardized sham operations reflecting conditions during major surgery. The study consisted of a pilot experiment designed to give high counts of sedimenting aerobic colony forming units (cfu). In a second main study, recording dust particles, air-borne and sedimenting aerobic cfu, the screen was associated with optimal operating room clothing. In the pilot experiment the use of the screen resulted in a substantial reduction of sedimenting bacteria from 3835-4940 to 0-390 cfu/m(2)/h. In the main study, the use of the additional LAF reduced the surface contamination from 416-329 to 7-78 cfu/m(2)/h up to 1.6 m from the screen (P=0.001-0.0001). Measured in the wound area the screen reduced the air counts of bacteria from 9-14 to 0.2-0.4 cfu/m(3) (P=0.008-0.0001) and a marked reduction of air-borne dust particles was recorded (P=0.007-0.009). In conclusion, the additional mobile LAF screen reduced the counts of aerobic air-borne and sedimenting bacteria-carrying particles as well as dust particles to the levels gained with complete ultra-clean LAF room ventilation. Thus, the screen might prove a valuable addition to operating room ventilation as well as in other areas where asepsis is essential.
منابع مشابه
The addition of a mobile ultra-clean exponential laminar airflow screen to conventional operating room ventilation reduces bacterial contamination to operating box levels.
A mobile screen producing ultra-clean exponential laminar airflow (LAF) was investigated as an addition to conventional turbulent/mixing operating room (OR) ventilation (16 air changes/h). The evaluation was performed in a small OR (50 m(3)) during 60 standardized operations for groin hernia including mesh implantation. The additional ventilation was used in 50 of the operations. The LAF passed...
متن کاملMobile zoned/exponential LAF screen - a promising new concept in ultra-clean air technology for additional operating room ventilation
A new concep t in the fo rm of a mobi le sc reen (0 .5 x 0 .4 m) produc ing u l t ra -c lean exponent ia l LAF (a i r f low cent ra l zone 0 .6 m/s and pe r iphera l zone 0 .4 m/s) was inves t iga ted as an addi t ion to convent iona l turbulent /mix ing opera t ing room vent i l a t ion . The evalua t ion was per formed dur ing s t r ic t ly s tandard ised sham opera t ions re f lec t ing cond...
متن کاملA mobile laminar airflow unit to reduce air bacterial contamination at surgical area in a conventionally ventilated operating theatre.
The aim of this study was to evaluate the efficacy of a mobile laminar airflow (LAF) unit in reducing bacterial contamination at the surgical area in an operating theatre supplied with turbulent air ventilation. Bacterial sedimentation was evaluated during 76 clean urological laparotomies; in 34 of these, a mobile LAF unit was added. During each operation, settle plates were placed at four poin...
متن کاملUltraviolet Radiation Compared to an Ultra - Clean Air Enclosure 813
Clean air in the operating room is important during joint replacement surgery. We compared monochromatic ultraviolet radiation of254 nm with the use ofa Charnley-Howorth air enclosure by bacterial air-sampling during 113 total hip arthroplasties. Air samples were taken continuously at the edge of the wound and every 15 minutes at a site 130 cm from the operating table. We also tested the effect...
متن کاملForced-air warming and ultra-clean ventilation do not mix: an investigation of theatre ventilation, patient warming and joint replacement infection in orthopaedics.
We investigated the capacity of patient warming devices to disrupt the ultra-clean airflow system. We compared the effects of two patient warming technologies, forced-air and conductive fabric, on operating theatre ventilation during simulated hip replacement and lumbar spinal procedures using a mannequin as a patient. Infection data were reviewed to determine whether joint infection rates were...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید
ثبت ناماگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید
ورودعنوان ژورنال:
- The Journal of hospital infection
دوره 50 4 شماره
صفحات -
تاریخ انتشار 2002