Frequency Response Analysis in Power Transformer for Detection of Winding Short-circuit using Quasi-static Finite Element and Circuit-based Method

نویسندگان

  • Mohammadreza Barzegaran
  • M. R. Barzegaran
  • M. Mirzaie
چکیده

Detecting and removing minor faults in power transformer winding is essential because minor faults may develop and lead to major faults and finally irretrievable damages occur. In this paper in order to detect the position of short-circuit in the winding, frequency response of the input impedance of a power transformer is analyzed. Common short-circuits are categorized and the results are compared, then the behavior of frequency response due to disk-disk short-circuit is investigated. To increase the accuracy of analysis, innovative approach in finite element analysis is offered. This approach termed Electromagnetic quasi-static considers both magnetic and electric characteristics of power transformer. Simulation is fulfilled by interconnecting between finite element analysis and circuit-based model for employing shortcircuit.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Recognition and Location of Power Transformer Turn to Turn Fault by Analysis of Winding Imposed Forces

Turn to turn fault is one of the major internal failures in the power transformers that if it is not quickly detected, can be extended and led to a complete transformer breakdown. So, the diagnosis and location of the turn to turn fault of the power transformer, as one of the most important equipment in the power system, is the main objective of this paper. For this purpose, a detailed model of...

متن کامل

Power Auto-transformer Mechanical Faults Diagnosis ‎Using Finite Element based FRA

Frequency response analysis (FRA) is a sensitive ‎method established for testing the mechanical integrity of ‎transformers. However, interpretation of FRA signature still ‎needs expert opinions and there is no FRA interpretation code ‎generally accepted. Various mechanical faults with different ‎extents on power transformers are required to aid FRA ‎interpretation. To address this challenge, in...

متن کامل

FEM based Reactance Computation for Transformer Winding Deformation Detection

Leakage reactance is one of the most important specifications in transformer that has significant impact on its overall design. Variation in leakage reactance serves as a diagnostic measure to indicate mechanical integrity of power transformers before and after a short circuit test that demonstrates mechanical strength of transformer windings. This paper presents an approach for leakage reactan...

متن کامل

Characterization of Power Transformer Electromagnetic Forces Affected by Winding Faults

Electromagnetic forces in power transformer windings are produced by interaction between the leakage fluxes and current passing them. Since the leakage flux distribution along the windings height is in two axial and radial directions, so the electromagnetic forces have two components, radial and axial. There is a risk that a large electromagnetic force due to the short circuit or inrush current...

متن کامل

Modeling the Frequency Response Movements in Power Transformers for Predicting Purposes

Power transformers are key components in electrical power supplies and their failure could cause severe consequences on continuity of service and also generates substantial costs. Identifying problems at an early stage, before catastrophic failure occurs, is a great benefit for reliable operation of power transformers. Frequency Response Analysis (FRA) is a new, well-known and powerful diagnost...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2013