Impacts of Static Pressure Reset on VAV System Air Leakage, Fan Power and Thermal Energy ───Part I: Theoretical Model and Simulation
نویسندگان
چکیده
As for a variable air volume (VAV) system, the air duct static pressure is a typical control variable maintained by modulating supply fan speed. The static pressure equals to the summation of the duct pressure loss downstream of the sensor to the terminal box and box inlet static pressure. Typically, the air duct static pressure is set as a constant set point based on the system design information and sensor location. However, under partial load conditions, the terminal box dampers have to be closed more since the required airflow is less than the design airflow which directly leads to much less pressure loss. Thus the static pressure set point should be reset lower in order to reduce fan power, avoid noise at terminal box dampers and box damper malfunction due to excessive pressure. Different static pressure reset schedules are reviewed and compared, considering the influence of outside air temperature on the building load, availability of the VAV box damper positions, the airflow ratio based static pressure reset has also applicable advantages over the existing constant static pressure set point and two typical reset methods. This paper presents the theoretical models to express the impacts of static pressure reset on fan airflow, fan head, air leakage, fan power and thermal energy for both pressure independent and pressure dependent boxes. The impacts are also demonstrated using the parametric analysis and numerical results to show the benefits of the static pressure reset including reducing fan power, cooling energy and heating energy.
منابع مشابه
Effect of Blade Design Parameters on Air Flow through an Axial Fan
The objective of this paper is the numerical study of the flow through an axial fan and examining the effects of blade design parameters on the performance of the fan. The axial fan is extensively used for cooling of the electronic devices and servers. Simulation of the three-dimensional incompressible turbulent flow was conducted by numerical solution of the (RANS) equations for a model. The S...
متن کاملA Comprehensive Approach to an Optimum Design and Simulation Model of a Mechanical Draft Wet Cooling Tower
The present paper describes the designing of a thermally and economically optimum mechanical draft counter-flow wet cooling tower. The design model allows the use of a variety of packing materials in the cooling tower toward optimizing heat transfer. Once the optimum packing type is chosen, a compact cooling tower with low fan power consumption is modelled within the known design variables....
متن کاملA Heuristic Supply Air Temperature Reset Strategy for VAV Systems Employing Variable-Capacity DX Cooling Equipment
This paper presents a generalized control heuristic to reset supply air temperature setpoints for DX units with capacity modulation and variable air flow. The heuristic is shown to work well for different DX systems with different compressor types and fan-duct combinations. Digital scroll and variable-speed compressors were considered and modeled using curve fits to manufacturer’s data. Evapora...
متن کاملOptimization of Energy Conservation Potential for VAV Air Conditioning System using Fuzzy based Genetic Algorithm
The objective of this study is to present the test results of variable air volume (VAV) air conditioning system optimized by two objective genetic algorithm (GA). The objective functions are energy savings and thermal comfort. The optimal set points for fuzzy logic controller (FLC) are the supply air temperature (Ts), the supply duct static pressure (Ps), the chilled water temperature (Tw), and...
متن کاملA Study on Performance of Solid Oxide Fuel Cell-Stirling Engine Cycle Combined System- Part I: SOFC Simulation by Programming in Matlab and Modeling in Hysys
In recent years, using new methods in utilization of energy resources has become necessary due to environmental pollution and restriction of energy resources. The hybrid system presented in this article produced power with SOFC and Stirling engine. The purpose is to analyze a 50 kW Solid Oxide Fuel Cell that could produce enough thermal energy for a 10 kW Stirling engine working in the hybrid s...
متن کامل