Mitigation of Asymmetrical Grid Faults in Induction Generator-Based Wind Turbines Using Constant Power Load
نویسندگان
چکیده
Constant power loads (CPLs), interfaced through active rectifiers can be used for improving the stability of induction generator (IG)-based wind turbines under balanced grid voltage dips by providing the reactive power. Under asymmetrical grid faults, the negative sequence voltage produces additional generator torque oscillations and reduces the lifetime of the installed equipment. This article explores the possibility of using a CPL for mitigation of unbalanced voltage dips in an AC distribution system in addition to consuming a constant active power. Unbalanced fault mitigation as an ancillary service by the load itself could greatly increase the stability and performance of the overall power system. A CPL control structure, capable of controlling the positive and negative sequence of the grid voltage is suggested. The simulation results clearly indicate the effects of compensating the positive and negative sequence of the grid voltage on the performance of IG based wind turbines. The maximum Fault Ride Through (FRT) enhancement has been given priority and is done by the compensation of positive sequence voltage. The remaining CPL current capacity is used to compensate the negative sequence voltage in order to reduce the additional torque ripples in the IG.
منابع مشابه
Low Voltage Ride Through Enhancement Based on Improved Direct Power Control of DFIG under Unbalanced and Harmonically Distorted Grid Voltage
In the conventional structure of the wind turbines along with the doubly-fed induction generator (DFIG), the stator is directly connected to the power grid. Therefore, voltage changes in the grid result in severe transient conditions in the stator and rotor. In cases where the changes are severe, the generator will be disconnected from the grid and consequently the grid stability will be attenu...
متن کاملEfficient low-voltage ride-through nonlinear backstepping control strategy for PMSG-based wind turbine during the grid faults
This paper presents a new nonlinear backstepping controller for a direct-driven permanent magnet synchronous generator-based wind turbine, which is connected to the power system via back-to-back converters. The proposed controller deals with maximum power point tracking (MPPT) in normal condition and enhances the low-voltage ride-through (LVRT) capability in fault conditions. In this method, to...
متن کاملPower Quality Improvement using STATCOM in Wind Farms with Constant Speed Induction Generator under Unbalanced Grid Faults
PG student, Dept of EEE, K.S.Rangasamy College of Technology, [email protected] Professor, Dept of EEE, K.S.Rangasamy College of Technology, [email protected] Abstract-This paper presents a mitigation of power quality problems such as shortage of reactive power, voltage fluctuations, voltage and current harmonics due to wind farms connected to the non linear loads. The fault occur ...
متن کاملGA-Based Optimal LQR Controller to Improve LVRT Capability of DFIG Wind Turbines
Nowadays, the doubly-fed induction generators (DFIGs) based wind turbines (WTs) are the dominant type of WTs connected to grid. Traditionally the back-to-back converters are used to control the DFIGs. In this paper, an Indirect Matrix Converter (IMC) is proposed to control the generator. Compared with back-to-back converters, IMCs have numerous advantages such as: higher level of robustness, re...
متن کاملModelling,Simulation And Analysis Of Doubly Fed Induction Generator For Wind Turbines
This paper refers to modeling, simulation and analysis of doubly fed induction generator for wind turbines. This paper presents the modelling of DFIG based WT system and the simulation results performed for the system developed in Simulink environment of MATLAB . A gird connected wind energy generation model is developed and simulated for normal operation and for some faults in the grid. the an...
متن کامل