Demand Controlled Filtration in an Industrial Cleanroom

نویسندگان

  • David Faulkner
  • Dennis DiBartolomeo
  • Duo Wang
چکیده

In an industrial cleanroom, significant energy savings were realized by implementing two types of demand controlled filtration (DCF) strategies, one based on particle counts and one on occupancy. With each strategy the speed of the recirculation fan filter units was reduced to save energy. When the control was based on particle counts, the energy use was 60% of the baseline configuration of continuous fan operation. With simple occupancy sensors, the energy usage was 63% of the baseline configuration. During the testing of DCF, no complaints were registered by the operator of the cleanroom concerning processes and products being affected by the DCF implementation. Introduction Demand controlled filtration (DCF) is a method of saving energy in cleanrooms by decreasing the recirculation fan speed when demand for filtration is low. A particle counter or an occupancy sensor can measure the demand for filtration. Another method of saving energy in cleanrooms is the use of programmable timers that decrease recirculation fan speeds when occupants are not expected, such as nights and weekends. DCF should not be confused with demand controlled ventilation, which is the control of outside air entering a building based on the demand due to occupancy and/or processes occurring in the building. In a past study, we found that industrial cleanroom users were hesitant to implement DCF, often because of concern that large changes in the recirculation fan speeds would produce a burst of particles discharged into the cleanroom. We have not seen this phenomenon in our previous or current study. Another concern is that for large manufacturing facilities, the potential loss of product outweighs any potential energy savings. There are many small research or industrial facilities that are not as productoriented that can benefit from the potential energy savings from implementing DCF. In the past few years there has been gathering interest in saving energy in cleanrooms and some businesses are experimenting with DCF. There is a large Southern California manufacturer with Class 100 (ISO Class 5) and 10,000 (ISO Class 7) cleanrooms covering about 15,000 ft. During non-working hours, the make-up and recirculation air handler fans at this facility are turned down to recirculate less air. A reduction in fan speed of about 30% at night, when the space is unoccupied, reduces the measured recirculation air handler power consumption from 32 kW to less than 9kW – a reduction of 75%. Another large manufacturing facility in Southern California is in the process of implementing active, real-time DCF using particle counters. The facility manager has received rebates from the local utility for implementing DCF. The particle counters have been purchased and preliminary testing has been done. The next steps are installing the particle counters and implementing the control routines. Finally, a large East Coast university recently modernized a building with cleanrooms. In the process they installed particle counters in every cleanroom area and plan to implement DCF. Energy savings potential The potential for energy savings is tremendous as fan energy has an approximately cubic relationship with fan speed. Thus, even a small reduction in fan speed can translate into large energy savings. Cleanrooms employing DCF can achieve lasting savings by implementing active control of the recirculation fans based on inputs from either a particle counter or an occupancy sensor. Also, cleanroom operators may be able to participate in demand response programs offered by utilities. During high electricity demand days, such as hot summer days, many utilities offer incentives to their customers, such as rebates or price reductions, to voluntarily reduce electricity demand at their facilities. Typically these programs ask customers to reduce electricity consumption for periods of 1-6 hours. As long as the cleanroom fans are equipped with variable frequency drives (VFD), then the recirculation fan speeds can be adjusted lower during critical demand days. A 10-20% reduction in recirculation fan speed can translate to a reduction in energy use of over 40%. Methods Facility Experiments were conducted to evaluate air quality in an industrial cleanroom in the San Francisco Bay Area while DCF was implemented. The cleanroom that was studied was one of a suite of four adjacent cleanrooms, each with different classifications from Class 10 (ISO Class 4) to Class 10,000 (ISO Class 7). The suite of cleanrooms was designed so that the inner Class 10 (ISO Class 4) cleanroom (Group-5) is at a higher pressure than the adjacent Class 100 (ISO Class 5) cleanroom (Group-6), which in turn is at higher pressure than the adjacent Class 1,000 (ISO Class 6) cleanroom (Group-3), etc., see Figure 1. There are open grilles for air to flow from the Group-5 cleanroom to the Group-6 cleanroom to the Group-3 cleanroom and finally to the Group-2 cleanroom. The cleanroom in which the experiments were conducted was the Group-2 area and was a Class 10,000 (ISO Class 7). The floor area of the entire suite is about 1600 ft and the floor area of the Group-2, the experimental cleanroom, was 600 ft. The layout of Group-2 is shown in Figure 2. Each cleanroom had air recirculated by ceiling-mounted 2 ft x 4 ft fan filter units with HEPA filters. The Group-2 cleanroom had 16 fan filter units covering about 20% of the ceiling area. There were 4 hoods in the middle of the cleanroom as well as 2-3 flow hoods at each end of the cleanroom. Airflow through these hoods were not controlled as a part of our study. Outside make-up air was controlled by a separate ventilation system and was not controlled in our study. Environmental conditions, temperature and humidity were controlled by a separate control and also were not part of our study. Before our study, a laptop computer using a proprietary software program controlled the cleanroom fan filter units. The software allowed control of the fan filter units individually or in groups. This software was used to lower the fan speeds to 50% at night (22:00 to 6:00) and on weekends. This software and corresponding laptop would occasionally fail and the fan filter units would run at the speed of the last valid command; the fan filter units are designed to always run at the last valid command. Thus, occasionally the fan filter units for all of the cleanrooms would run for several days at 50% speed before the problem was discovered. After implementing the night and weekend energy reduction, particle concentrations at 4 locations in the cleanroom suite were recorded continuously for background data. The particles concentrations were measured with MetOne 237B particle counters (Hach Ultra, Grants Pass, OR) capable of counting particles in 6 size bins from 0.3 to 5 microns at a sample flow rate of 0.1 cfm. Some particle counters were moved to different locations within the cleanroom suite during the background measurements. Based on this data and the desires of the facility manager, the experiments were performed in the Group-2 cleanroom which was the Class 10,000 (ISO Class 7) cleanroom. After background particle measurements were recorded, a particle counter was placed in the study cleanroom (Group-2) near the center of the room on a countertop about 3 ft above the floor. To implement DCF, the particle counter was connected to a laptop computer running an off-the-shelf software program, LabVIEW Version 5.1 (National Instruments). Control routines in LabVIEW had been developed to record particle counts, and use the particle count information to decide whether to increase or decrease fan speeds. The particle counter sent counts to the laptop every 30 seconds and the particle counts in the 0.3 and 0.5 micron size bins were compared to established upper limits. The fan speed was either increased or decreased until either the maximum or minimum fan speed was reached. A record of the fan speed, particle counts and other parameters were recorded every 60 seconds in LabVIEW. After implementing DCF with the particle counter, we implemented DCF with control based on occupancy. The strategy was simple; if there were occupants detected, then the fan filter units were set to the programmed maximum speed, and after 30 minutes of no occupancy detected, the fans were set to 50% of programmed maximum speed. There were 6 wireless infrared battery-operated occupancy sensors placed in the cleanroom. The 6 sensors were mounted on the walls so that each work area and traffic lane was covered by at least one occupancy sensor. A wireless signal was sent from the occupancy sensors to the laptop and the above strategy was implemented. The data from the particle counter was converted to an equivalent ISO Class using the following equation (ISO 14644-1: 1999(E)): ( ) 08 . 2 1 . 0 10 D N n C = (1) where, Cn is the maximum permitted concentration (in particles per cubic meter of air) of airborne particles that are equal to or larger than the considered particle size. Value is rounded to the nearest whole number, using no more than three significant figures. N is the ISO classification number, which shall not exceed a value of 9. Intermediate ISO classification numbers may be specified; with 0.1 the smallest permitted increment of N. D is the considered particle size, in micrometers, which was 0.3 μm in this study. 0.1 is a constant, with a dimension of micrometers. With algebraic manipulation equation (1) can be rearranged to solve for N, the ISO classification number: ( ) D C N n 10 10 log 1 08 . 2 log + + = (2)

برای دانلود رایگان متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Energy Savings in Cleanrooms from Demand-controlled Filtration

In cleanrooms, very low particle concentrations are maintained by recirculation of air at a high rate (e.g., 600 room air volumes per hour) through highly efficient air filters. We report results in a Class M3.5 (Class 100) cleanroom with 28 m (300 ft) floor area, where significant energy savings were realized by controlling the rate of air recirculation through the filters in response to real-...

متن کامل

Efficiency of Electrocoagulation, Sedimentation and Filtration Hybrid Process in Removing Chemical Oxygen Demand and Turbidity from Carwash Industrial Wastewater: Optimization by Response Surface Methodology

Background and purpose: Nowadays, rapid growth of car wash industries has led to a demand for wastewater reclamation. In this study, the hybrid process including electrocoagulation/flotation, sedimentation, and filtration were used in treatment of real carwash wastewater. Materials and methods: In this research, the sample was first entered into the ECF reactor, then entered the retention tank...

متن کامل

Capability Maturity Model Software Development using Cleanroom Software Engineering Principles - Results of an Industry Project

The Capability Maturity Model (CMM) for Software is a development framework that describes the key elements for an effective software process. Cleanroom software engineering (CSE) is a managerial and engineering process for the development of high quality software with certified reliability. The combination of CMM management and organizational capabilities and the judicious application of Clean...

متن کامل

Cleanroom Maintenance Significantly Reduces Abundance but Not Diversity of Indoor Microbiomes

Cleanrooms have been considered microbially-reduced environments and are used to protect human health and industrial product assembly. However, recent analyses have deciphered a rather broad diversity of microbes in cleanrooms, whose origin as well as physiological status has not been fully understood. Here, we examined the input of intact microbial cells from a surrounding built environment in...

متن کامل

An Industrial Application of Cleanroom Software Engineering - Benefits through Tailoring

Cleanroom is a set of software engineering principles that support the development of reliable software. The Systems group at Raytheon TI Systems, a SEI level 3 organization, successfully adopted Cleanroom into a pilot CMM level 5 project. The successful introduction of this technology was a result of the principles of Cleanroom being based on fundamental computer science foundations. As with a...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2007