Influence Analysis and Prediction of ESDD and NSDD Based on Random Forests
نویسندگان
چکیده
Equivalent salt deposit density (ESDD) and non-soluble deposit density (NSDD) measurements are a basic requirement of power systems. In order to predict the site pollution severity (SPS) of insulators, a new method based on random forests (RFs) is proposed. Using mutual information (MI) theory and RFs, the weights of factors related to the SPS of insulators are analyzed. The samples of contaminated insulators are extracted from the transmission lines of high voltage alternating current (HVAC) and high voltage direct current transmission (HVDC). The regression models of RFs and support vector machines (SVM) are constructed and compared, which helps to support the lack of information in predicting NSDD in previous works. The results are as follows: according to the mean decrease accuracy (MDA), mean decrease Gini, (MDG), and MI, the types of the insulators (including surface area, surface orientation, and total length) as well as the hydrophobicity are the main factors affecting both ESDD and NSDD. Compared with NSDD, the electrical parameters have a significant effect on ESDD. For the influence factors of ESDD, the weights of the insulator type, hydrophobicity, and meteorological factors are 52.94%, 6.35%, and 21.88%, respectively. For the influence factors of NSDD, the weights of the insulator type, hydrophobicity, and meteorological factors are 55.37%, 11.04%, and 14.26%, respectively. The influence voltage level (vl), voltage type (vt), polarity/phases (pp) exerted on ESDD are 1.5 times, 3 times, and 4.5 times of NSDD, respectively. The influence that distance from the coastline (d), wind velocity (wv), and rainfall (rf ) exert on NSDD are 1.5 times, 2 times, and 2.5 times that of ESDD, respectively. Compared with the natural contamination test and the SVM regression model, the RFs regression model can effectively predict the contamination degree of insulators, and the relative error of the predicted ESDD and NSDD is 8.31% and 9.62%, respectively.
منابع مشابه
Analysis of Flashover Voltages of Disc Type Insulator under Artificial Pollution Condition (TECHNICAL NOTE)
Through this paper work we have analyzed the effect of different contaminants on the flashover by creating artificial pollution condition, considering the natural condition where more than one salt as contaminant deposits on the surface of insulator at a time, under the wet condition that cause flow of highly leakage current, that leads to flashover. We choses the mixture of different salts, so...
متن کاملInvestigating the Effect of Rainfall Parameters on the Self-Cleaning of Polluted Suspension Insulators: Insight from Southern China
The cleaning effect of heavy rain (the rainfall reaches 5 mm every day) on surface contamination of insulators is more effective than dew, fog, mist, and other light rain conditions which can initiate leakage currents and increase the likelihood of flashover. It is well understood that heavy rain can wash away contamination from the surface of high voltage (HV) insulators and thereby reduce the...
متن کاملA Comparative Study on Contamination Deposited Characteristics of ±800kV DC Line Insulators
This report describes the natural contamination test results of ±800kV line insulators at high altitudes. Natural exposure tests with -816kV DC voltage energization were carried out at National Engineering Laboratory for UHV Engineering Technology (Kunming).The results showed that the strain type and V-type insulator strings show a lighter pollution and the insulators with a better aerodynamic ...
متن کاملComparison of Survival Forests in Analyzing First Birth Interval
Background and objectives: Application of statistical machine learning methods such as ensemble based approaches in survival analysis has been received considerable interest over the past decades in time-to-event data sets. One of these practical methods is survival forests which have been developed in a variety of contexts due to their high precision, non-parametric and non-linear nature. This...
متن کاملاندازه گیری صنعتی تاثیر آلودگی بر عملکرد عایقهای فشار قوی
مقرههای فشار قوی در معرض شرایط محیطی و اقلیمی مختلف قرار میگیرند. تأثیرات متقابل شرایط محیطی و آلودگی ایزولاسیون باعث میگردد عایق مقرهها خود بستر مناسبی جهت هدایت جریان گردیده و اثرات خود را بر سیستمهای قدرت به جا بگذارد. در حال حاضر جهت تعیین سطح آلودگی محیط بر روی ایزولاسیون از اعداد تقریبی و تجربی استفاده میگردد. در نتیجه فواصل خزشی در بعضی مناطق با شرایط محیط متناسب نبوده و زیر حد طرا...
متن کامل