Power Transformers Differential Protection Using the p-q Power Theory
نویسندگان
چکیده
This paper describes the application of the p-q power theory to the differential protection of power transformers. The information provided by the harmonic content of the differential active and reactive power components is used to detect winding insulation failures and to distinguish them from magnetizing inrush current transients. A variety of test cases is presented in the paper, demonstrating the effectiveness of the protection strategy.
منابع مشابه
Determination of a new model to study ultra-saturation phenomenon during the loaded power transformer energization and its effect on differential protection
One of transient phenomenon that causes the mal-operation of the power transformer differential protection during the energization of a loaded power transformer is the ultra-saturation phenomenon. In this paper, a new model for investigating the ultra-saturation phenomenon during the energization of a loaded power transformer is presented and its effect on the differential protection of the pow...
متن کاملDetermination of a new model to study ultra-saturation phenomenon during the loaded power transformer energization and its effect on differential protection
One of transient phenomenon that causes the mal-operation of the power transformer differential protection during the energization of a loaded power transformer is the ultra-saturation phenomenon. In this paper, a new model for investigating the ultra-saturation phenomenon during the energization of a loaded power transformer is presented and its effect on the differential protection of the pow...
متن کاملA New Model for Analysis of Unusual Mal-Operation of Differential Protection Due to the Ultra-Saturation Phenomenon during the Loaded Power Transformer Energization
In this paper, a new model based on the thevenin equivalent circuit for investigating the ultra-saturation phenomenon during the energization of a loaded power transformer is presented and its effect on the differential protection of the transformer is considered. The ultra-saturation phenomenon causes the mal-operation of the power transformer differential protection. So, the description a...
متن کاملtransformer differential protection using the fault-generated high-frequency transient components
Power transformers are the most important components of a power system, so their protection is a critical issue. This paper proposes a novel and efficient algorithm based on the high-frequency components of the differential current signal to discriminate between the magnetizing inrush currents and the internal faults. After detecting the over-current in the differential current signals, samples...
متن کاملA New Model for Analysis of Unusual Mal-Operation of Differential Protection Due to the Ultra-Saturation Phenomenon during the Loaded Power Transformer Energization
In this paper, a new model based on the thevenin equivalent circuit for investigating the ultra-saturation phenomenon during the energization of a loaded power transformer is presented and its effect on the differential protection of the transformer is considered. The ultra-saturation phenomenon causes the mal-operation of the power transformer differential protection. So, the description a...
متن کامل