Partial Discharge Detection and Localization in High Voltage Transformers Using an Optical Acoustic Sensor
نویسنده
چکیده
A partial discharge (PD) is the dissipation of energy caused by the buildup of localized electric field intensity. In high voltage devices such as transformers, this buildup of charge and its release can be symptomatic of problems associated with aging, such as floating components and insulation breakdown. This is why PD detection is used in power systems to monitor the state of health of high voltage transformers. If such problems are not detected and repaired, the strength and frequency of PDs increases and eventually leads to the catastrophic failure of the transformer, which can cause external equipment damage, fires and loss of revenue due to an unscheduled outage. Reliable online PD detection is a critical need for power companies to improve personnel safety and decrease the potential for loss of service. The PD phenomenon is manifested in a variety of physically observable signals including electric and acoustic pulses and is currently detected using a host of exterior measurement techniques. These techniques include electrical lead tapping and piezoelectric transducer (PZT) based acoustic detection. Many modern systems use a combination of these techniques because electrical detection is an older and proven technology and acoustic detection allows for the source to be located when several sensors are mounted to the exterior of the tank. However, if an acoustic sensor could be placed inside the tank, not only would acoustic detection be easier due to the increased signal amplitude and elimination of multipath interference, but positioning could also be performed with more accuracy in a shorter time. This thesis presents a fiber optic acoustic sensing system design that can be used to detect and locate PD sources within a high voltage transformer. The system is based on an optical acoustic (OA) sensor that is capable of surviving the harsh environment of the transformer interior while not compromising the transformer’s functionality, which allows for online detection and positioning. This thesis presents the theoretical functionality and experimental validation of a band-limited OA sensor with a usable range of 100-300 kHz, which is consistent with the frequency content of an acoustic pulse caused by a PD event. It also presents a positioning system using the time difference of arrival (TDOA) of the acoustic pulse with respect to four sensors that is capable of reporting the three-dimensional position of a PD to within ±5cm on any axis. This work was supported in part by NSF grant 9810688.
منابع مشابه
An ultra-sensitive optical MEMS sensor for partial discharge detection
A diaphragm-based interferometric fiber optical microelectromechanical system sensor with high sensitivity is designed and tested for on-line detection of the acoustic waves generated by partial discharges (PD) inside high-voltage power transformers. In principle, the sensor is made according to Fabry Perot interference, which is placed on a micro-machined rectangular silicon membrane as a pres...
متن کاملDetection and wavelet analysis of partial discharges using an optical fibre interferometric sensor for high-power transformers
The main problem in power transformers is the degradation of the isolation, and partial discharges are a major contribution to this shortcoming. Partial discharges inside mediumand high-power transformers generate ultrasonic pressure waves which are usually detected by using acoustic piezoelectric sensors placed outside the transformers. In this paper we describe an optical fibre interferometri...
متن کاملAn Optic Fiber Sensor for Partial Discharge Acoustic Detection
AN OPTIC FIBER SENSOR FOR PARTIAL DISCHARGE ACOUSTIC DETECTION by Xiaodong Wang Partial discharge (PD) is a very common problem in operating power transformers and is one of the factors that could lead to failure of power transformers, leading to power outage and expensive repairs. The acoustic wave induced by PD can be measured and used for monitoring, diagnosing, and locating potential failur...
متن کاملCharacterization of Medium Voltage Equipment Ageing by Monitoring of Partial Discharges Chemical and Acoustical Emission
During the ageing of in-service medium voltage equipment, electrical losses are mainly due to partial discharges. These partial discharges can lead to the electrical failure of industrial equipment [1]. Partial discharges include (i) bulk discharges occurring in insulating material voids, (ii) corona discharges affecting or not the insulator and (iii) surface discharges developing on an insulat...
متن کاملA Novel Defect Classification System of Cast-Resin Transformers by Neural Network under Acoustic Emission Signal
Degraded insulating property of electric equipments will lead to serious accident and great loss for the utilities and customers. Partial discharge detection is an efficient diagnosis method to prevent the failure of electric equipments arising from degrading insulation. However, universal offline partial discharge detection could be performed only during shutdown of equipments. By using the pr...