A mixed integer programming model for optimal fault section estimation in power systems
نویسندگان
چکیده
This paper proposes a methodology to deal with the fault section estimation problem in electrical power systems. The main motivation for this study lies in the fact that operators of control centers usually are subject to information overload during great contingencies. The fault diagnosis is formulated as an optimization problem and solved through two stages: classification of events at equipment level and the fault section estimation. The first stage consists of a heuristic based on Bayes’ theorem that provide the input to the second stage where a mixed integer programming model is solved by commercial package in order to determine the faulted section. Several fault scenarios from a real Southern Brazilian subsystem were considered to validate the methodology. The results show that the proposed method can correctly identify the faulted section even in case of multiple faults or in case of improper operation of protective
منابع مشابه
A Mixed Integer Programming Approach to Optimal Feeder Routing for Tree-Based Distribution System: A Case Study
A genetic algorithm is proposed to optimize a tree-structured power distribution network considering optimal cable sizing. For minimizing the total cost of the network, a mixed-integer programming model is presented determining the optimal sizes of cables with minimized location-allocation cost. For designing the distribution lines in a power network, the primary factors must be considered as m...
متن کاملFeasibility study of presenting a dynamic stochastic model based on mixed integer second-order conic programming to solve optimal distribution network reconfiguration in the presence of resources and demand-side management
Nowadays, with the use of devices such as fossil distributed generation and renewable energy resources and energy storage systems that are operated at the level of distribution networks, the problem of optimal reconfiguration has faced major challenges, so any change in the power of this resources can have different results in reconfiguration. Similarly, load changes during the day can lead to ...
متن کاملOptimal Setting Sor Under Frequency Load Shedding Relays Using Mixed Integer Linear Programming
After occurrence of some disturbances in power system that causes the sever imbalance between generation power and electrical load, the power system frequency begins to decrease. To prevent power system frequency instability and stop the frequency decay below the power system allowable frequency limitation, load shedding schemes should be utilized by applying under frequency load shedding relay...
متن کاملObservability-Enhanced PMU Placement Considering Conventional Measurements and Contingencies
Phasor Measurement Units (PMUs) are in growing attention in recent power systems because of their paramount abilities in state estimation. PMUs are placed in existing power systems where there are already installed conventional measurements, which can be helpful if they are considered in PMU optimal placement. In this paper, a method is proposed for optimal placement of PMUs incorporating conve...
متن کاملA two-stage stochastic programming model for the optimal sizing of hybrid PV/diesel/battery in hybrid electric ship system
Ships play the major role in bulk transportation and they need their special energy system. This paper proposes a stochastic programing method for optimal sizing of a hybrid ship power system with energy storage system (ESS), photovoltaic power (PV) and diesel generator. To account for uncertainties, in this study a two-stage stochastic mixed-integer non-linear programing is used to model the o...