Fluid dynamics of cytotoxic safety cabinets.
نویسندگان
چکیده
This study investigated the specific fluid dynamics characteristics of cytotoxic safety cabinets (CSC), particularly those used in cancer drug reconstitution operations. Measurements taken on site were used to derive characteristic data for these cabinets. An in-depth laboratory investigation of airflows inside another CSC was also conducted. Anemometric values recorded on these two installations enabled the experimental validation of computational fluid dynamics methods applied to CSC. The digital flow simulations conducted provide a better understanding of the detailed flow structure inside a CSC and made it possible to study the influence of different operating parameters on the air velocity distribution inside the cabinet front opening: recycled air temperature, product protection airflow rate, suction openings spatial distribution, air compensation mode and draughts, operator arm penetration, and operator presence in front of the cabinet.
منابع مشابه
CFD-Calculation of Fluid Flow in a
An accurate description of the fluid flow and heat transfer within a Pressurized Water Reactor (PWR), for the safety analysis and reactor performance is always desirable. In this paper a mathematical model of the fundamental physical phenomena which are associated to a typical PWR is presented. The mathematical model governs the fluid dynamics in the reactor. Using commercial software CFX, a co...
متن کاملAnalysis of Chlorine Gas Incident Simulation and Dispersion Within a Complex and Populated Urban Area Via Computation Fluid Dynamics
In some instances, it is inevitable that large amounts of potentially hazardous chemicals like chlorine gas are stored and used in facilities in densely populated areas. In such cases, all safety issues must be carefully considered. To reach this goal, it is important to have accurate information concerning chlorine gas behaviors and how it is dispersed in dense urban areas. Furthermore, mainta...
متن کاملPerformance of exhaust-protective (class I) biological 'safety' cabinets.
Nineteen open-fronted (class I) safety cabinets were subjected to spore containment and airflow tests, which suggested that a flow of 0.75 m/s was the minimum required for safe operation; further tests on three of the cabinets were repeated at different air speeds and confirmed this. The airflow is required to overcome the effect of laboratory or external air currents. Contamination of surfaces...
متن کاملNursing best practices using automated dispensing cabinets: nurses' key role in improving medication safety.
Automated dispensing cabinets (ADCs) are used widely, but safety gaps remain. Nursing-pharmacy collaboration, expert guidance, self-assessment tools, compliance with nursing best practices, and continuing education are essential to optimize the safety and productivity of ADC use.
متن کاملEvidence Briefings on Interventions to Improve Medication Safety
The use of automated dispensing systems (ADS), also known as automated dispensing cabinets (ADC), unit-based cabinets (UBC), automated dispensing devices (ADD), automated distribution cabinets and automated dispensing machines (ADM), in hospitals is increasing. In 2011, 40% of US hospital pharmacies had a decentralised inpatient medication distribution system and 89% of those used ADS 1. There ...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید
ثبت ناماگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید
ورودعنوان ژورنال:
- The Annals of occupational hygiene
دوره 54 2 شماره
صفحات -
تاریخ انتشار 2010