This paper presents the design of earthing system for 132 KV substation and simulation for calculation of required parameters. This paper is to provide information pertinent to safe earthing practices in ac substation design and to establish the safe limits of potential difference under normal and fault conditions. The grounding grid system of a practical 220 kV substation is calculated by MATLAB program. The supporting data has been obtained from actual field tested at the substation. Standard equations are used in the design of earthing system to get desired parameters such as touch and step voltage criteria for safety, earth resistance, grid resistance, maximum grid current, minimum conductor size and electrode size, maximum fault current level and resistivity of soil. By selection the proper horizontal conductor size, vertical electrode size and soil resistivity, the best choice of the project for safety is performed. This paper mentions the calculation of the desired parameters which are simulated by MATLAB program. Some simulated results are evaluated.
منابع مشابه
HV Substation Earthing Design for Mines
-High Voltage (HV) substation forms important assets for the mining industries. The existences of these substations necessitate earthing design to ensure safety compliance to the mine regulations. The HV system within the mines is consisted of multiple substations which are connected throughout and underground cable. These substations provide the load with the required electrical power to perfo...
متن کاملEffect of Integrity of the Earthing System on the Rise of Earth Potential
This paper investigates the effects of breaks in bonds, breaks in the earthing system and breaks in earth wire on the rise of the earth potential (EPR) in a substation and at the transmission tower bases using various models of an L6 tower. Different approaches were adopted to examine the integrity of the earthing system and the terminal towers. These effects were investigated to see the associ...
متن کاملReliability assessment of power distribution systems using disjoint path-set algorithm
Finding the reliability expression of different substation configurations can help design a distribution system with the best overall reliability. This paper presents a computerized a nd implemented algorithm, based on Disjoint Sum of Product (DSOP) algorithm. The algorithm was synthesized and applied for the first time to the determination of reliability expression of a substation to determine...
متن کاملCalculation of earthing and screening effects of compensation conductor laid alongside underground multi-cable power lines
Power substations in an urban area are interconnected by high voltage underground power cables, resulting also in interconnections of their earthing grids through cable metallic screens/sheaths. Most modern power cables with XLPE insulated core have metallic screens which are practically insulated from ground. These screens can only be (and usually are) grounded at cable ends and therefore do n...
متن کاملOptimal Design of Grounding System for HV/ EHV Substations in Two Layered Soil
Successful operation of entire power system depends to a considerable extent on efficient and satisfactory performance of substations. Hence substations in general can be considered as heart of overall power system. In any substation, a well designed grounding plays an important role. Since absence of safe and effective grounding system can result in mal-operation or non-operation of control an...