High-Frequency Spectrum Analysis of VFTO Generated inside Gas Insulated Substations
نویسنده
چکیده
Worldwide many electrical equipment insulation failures have been reported caused by switching operations, while those equipments had previously passed all the standard tests and complied with all quality requirements. The problem is mostly associated with high-frequency overvoltages generated during opening or closing of a switching device. The transients generated during switching operations in a Gas Insulated Substation (GIS) are associated with high frequency components in the order of few tens of MHz. The frequency spectrum of the VFTO generated in the 220/66 kV Wadi-Hoff GIS is analyzed using Fast Fourier Transform technique. The main frequency with high voltage amplitude due to the operation of disconnector (DS5) is 5 to 10 MHz, with the highest amplitude at 9 MHz. The main frequency with high voltage amplitude due to the operation of circuit breaker (CB5) is 1 to 25 MHz, with the highest amplitude at 2 MHz. Mitigating techniques damped the oscillating frequencies effectively. The using of cable terminal reduced the frequency oscillation effectively than that of OHTL terminal. The using of a shunt capacitance results in vanishing the high frequency components. Ferrite rings reduces the high frequency components effectively especially in the range 2 to 7 MHz. The using of RC and RL filters results in vanishing the high frequency components. Keywords—GIS, VFTO, Mitigation Techniques, Frequency spectrum, FFT, EMTP/ATP.
منابع مشابه
Effect of Very Fast Transient over voltages at high frequency in a Gas Insulated Substation during switching operations
Due to the opening or closing of circuit breakers and disconnect switches in Gas Insulated Substations (GIS), especially in the pumped storage power stations, Very Fast Transient Over-voltages (VFTO) are generated. This paper describes the 500 kV and 750 kV GIS. The variations of VFTO magnitudes at different points in 500 kV and 750 kV GIS during different switching operations have been calcula...
متن کاملNanocrystalline to Suppress VFTO and VFTC for 245kV Gas Insulated Substations
Switching of disconnectors (DS) and various faults in Gas Insulated Substation (GIS) causes number of pre-strikes and re-strikes happens. The short duration voltage collapse, traveling surges in busbar causes Very Fast Transient Over voltages (VFTO) and Very fast Transient Currents (VFTC) in the GIS substation. The main challenge is to reduce VFTO and VFTC amplitudes. Several methods have been ...
متن کاملNew mitigation methods for transient overvoltages in gas insulated substations
During switching of disconnectors (DS) in GIS a varying number of pre-strikes and re-strikes occur. Due to the very short duration of the voltage collapse, traveling surges are generated in the busbar duct. These very fast transient overvoltages (VFTO) can become the limiting dielectric stress which defines the dimensions at UHV voltage levels. The decision shall be based on the maximum VFTO pe...
متن کاملMitigation of Transient Overvoltages Generated Due to Switching Operations and Lightning in Gas-insulated Substation (GIS) Without Extra Limiter
Gas-insulated substations (GIS) have different specifications in proportion to air-insulated substations. Transformer failures related to lightning and switching are often reported in the gas insulated substation (GIS). This problem is the voltage magnifications due to reflections of switching and lightning surges at various junctions within the GIS. thereby overvoltages in GIS are more importa...
متن کاملAnalysis of effective factors on transient ground potential rise in gas insulated substations
This study presents the manner in which transient modeling concepts, which are fully analyzed in the referred standards, are implemented, for the purpose of evaluating the Transient Ground Potential Rise (TGPR). This is a phenomenon of 10–100kV voltages with up to 10μs duration on the grounded enclosure of Gas Insulated Substations (GIS), which may cause concern for personnel safety and problem...