Feasibility Assessment on Vacuum Insulated Switchgear
نویسندگان
چکیده
To find feasible alternatives to the use of SF6 in medium voltage switchgear equipment, AREVA T&D and Tsinghua University has started a cooperation to investigate the feasibility of using vacuum. This paper focused on three main points of the design of the Vacuum Insulated Switchgear (VIS): the maintainability of vacuum system, the insulation performance, and the thermal behavior under operating conditions. In our work, such steps were followed: literature review, basic designs, calculation and analysis. The investigation results showed the feasibility of 40.5 kV/2 kA VIS, assuming that the thermal design and material choice are done carefully in order to fulfill the requirements: insulation rating, life time and rated current. Whereas, for High Voltage switchgear equipment, 126kV or higher voltage level, further experimental research work is still needed. Key-Words: Vacuum Insulated Switchgear; Vacuum insulation; Vcuum lifetime; Vcuum thermal performance
منابع مشابه
Status Review on Gas Insulated Switchgear Partial Discharge Diagnostic Technique for Preventive Maintenance
Gas insulated switchgear (GIS) plays a vital role in high voltage transmission of electrical energy due to its advantages of high reliability and performance, compact in dimensions and outstanding compatibility with the environment. It uses sulphur hexafluoride gas as its insulant and coolant because of its high dielectric strength and excellent arc quenching ability. Gas insulated switchgear i...
متن کاملDielectric Properties of Gases Suitable for Secondary Medium Voltage Switchgear
SF6 is the dominating technology for gas insulated switchgear due to its excellent dielectric, thermal and arc quenching properties. Unfortunately, SF6 suffers from a very high global warming potential (GWP). Even though medium voltage switchgear is sealed for life with less than 0.1% emissions per year, the EU has specifically targeted SF6 for replacement in medium voltage switchgear for secon...
متن کاملChemical by-Product Diagnostic Technique for Gas Insulated Switchgear Condition Monitoring
Chemical by product diagnostic technique is an efficient, cost-effective and reliable diagnostic technique for gas insulate switchgear condition monitoring in view of its high sensitivity and antiinternal and external electromagnetic interference and noise. In this research paper, coaxial simulated gas insulated switchgear chamber and four different types of artificial defect were designed to c...
متن کاملبررسی عملکرد انواع سیستمهای عایقبندی در مخازن ذخیره پیشرانههای کرایوژنیک
The design of cryogenic propellant tanks that are used for storing liquid hydrogen and liquid oxygen due to the low boiling temperature has many differences compared with the others. In this paper, the most important insulated systems in cryogenic storage tanks, such as vacuum insulated, vacuum insulated with powder, vacuum insulated with radiation shields, multilayer super insulation an...
متن کاملNew 550-kV Gas-insulated Switchgear
OVERVIEW: Hitachi has developed smaller and more reliable gas-insulated switchgear (GIS) in response to demands for lower costs and stable power supplies. Reliability of this GIS was improved and the enclosure diameter was reduced in order to minimize the installation space by using new analysis techniques and rationalization in insulation design and in temperature rise criteria. Furthermore, t...
متن کامل