Effects of Condensate and Initial Formation of Thin Frost Layer on Evaporator Coil Performance of Room Air-Conditioners
نویسندگان
چکیده
This study investigated experimentally and theoretically, how condensate and initial formation of a thin frost layer on the surface of the evaporator affects the evaporator performance of room air-conditioners compared to dry coil conditions. The theoretically obtained results were validated with the measured values in both wet and initial frost formation conditions and a good correlation was found. The results indicated that, at the same range of change in face velocity value, the total conductivity of a dry coil (UA) dry is increased by 38.8%. However, when it is combined with an increase in latent heat to the evaporator total cooling capacity ratio value (Qlat/Q) of 10.6%, the total conductivity of wet coil (UA) wet is 45.4%. These results clearly indicate that the evaporator coil is characterized by higher performance under wet conditions compared to dry coil conditions. The results also show that the total conductivity after initial formation of a thin frost layer (UA) Fr has a higher value by about 8.2% than the dry coil condition. Moreover, the degradation in the evaporator coil performance under thin frost with a thickness up to one mm is only about 6.7%. © 2007 Jordan Journal of Mechanical and Industrial Engineering. All rights reserved
منابع مشابه
Design and Experimentation of Roll Bond Evaporator for Room Air Conditioner with R-22 as Refrigerant
The world is looking towards producing products which consume less power without compromising on quality of life. The increase in use of refrigeration and air conditioning appliances are contributing to global warming. The world wide temperatures are shooting up at an increasing rate. This paper presents a design of roll bond evaporator as the heat exchanger to provide cooling in room air condi...
متن کاملQualitative and quantitative study of water obtained from condensate atmosphere humidity in Bandar Abbas air conditioners
Introduction: Earth's atmosphere contains billion cubic meters of fresh water, which is considerable as a reliable water resource, especially insultry areas. What is important in this context, how to extract the water, in an economic manner. In order to extract water from air conditioner, no need to spend any cost, because water produced as a by-product and trouble production. The aim of study ...
متن کاملEffect of Using Evaporative Condenser Instead of Air Condenser in Window-air Conditioners
In this paper, the application of evaporative cooling for refrigeration cycle to reduce power consumption in hot climates is emphasized. Experimental and analytical investigations were performed in order to specify the effect of evaporative cooling condenser instead of the commonly used air cooling condenser in window-air-conditioners. Evaporative condenser can reject more heat, thereby preve...
متن کاملEffect of Using Evaporative Condenser Instead of Air Condenser in Window-air Conditioners
In this paper,
 the application of evaporative cooling for refrigeration cycle to reduce power consumption in hot climates is emphasized. Experimental and analytical investigations were performed in order to specify the effect of evaporative cooling condenser instead of the commonly used air cooling condenser in window-air-conditioners. Evaporative condenser can reject more heat, thereby pre...
متن کاملDirty Air Conditioners: Energy Implications of Coil Fouling
Residential air conditioning is responsible for a substantial amount of peak electrical demand and energy consumption throughout most of the United States. Coil fouling, the deposition of indoor dusts and other particulate matter on evaporator heat exchangers, increases system pressure drop and, correspondingly, decreases system air flow and air conditioner performance. In this paper, we apply ...
متن کامل