A Hybrid Optimization Algorithm (IA-PSO) for Optimal Coordination of Directional Overcurrent Relays in Meshed Power Systems

نویسندگان

  • MOHAMED ZELLAGUI
  • AHMED HASSAN
چکیده

This paper presents a hybrid optimization approach for the optimal coordination of Inverse Definite Minimum Time (IDMT) directional overcurrent relays in meshed power systems, namely Immune Algorithm and Particle Swarm Optimization (IA-PSO) algorithm. The algorithm is employed by coupling the immune information processing mechanism with the particle swarm optimization algorithm in order to achieve a better global solution with less computational effort. In protection coordination problem, the objective function to be minimized is the sum of the operating time of all main relays. The optimization problem is subject to a number of constraints which are mainly focused on the operation of the backup relay, which should operate if a primary relay fails to respond to the fault near to it, Time Dial Setting (TDS), Plug Setting (PS) and the minimum operating time of a relay. The proposed optimization algorithm aims to minimize the total operating time of each protection relay. Two systems are used as case study to check the efficiency of the optimization algorithm which are IEEE 4-bus and IEEE 6-bus models. Results are obtained and presented for IA and PS and IA-PSO algorithms. The obtained results for the studied cases are compared with those results obtained when using other optimization algorithms which are Teaching Learning-Based Optimization (TLBO), Chaotic Differential Evolution Algorithm (CDEA) and Modified Differential Evolution Algorithm (MDEA). From analysing the obtained results, it has been concluded that IA-PSO algorithm provides the most optimum solution with the best convergence rate. Key-Words: Meshed Power Systems, Directional Overcurrent Protection Relays, Optimal Coordination, Immune Algorithm, Particle Swarm Optimization, Hybrid Optimization Algorithms.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

CTpr-rating Primary rating of CT Irelay Current seen by the relay OF Objective function TDSmin Minimum value for TDS TDSmax Maximum value for TDS

1841 M. Zellagui & A.Y. Abdelaziz, Optimal Coordination of Directional Overcurrent Relays using Hybrid PSO-DE Algorithm  Abstract — This paper presents a new approach for the optimal coordination of IDMT directional overcurrent relays in meshed power systems using a hybrid particle swarm optimization based differential evolution algorithm (PSO-DE). In protection coordination problem the total ...

متن کامل

Considering Pilot Protection in the Optimal Coordination of Distance and Directional Overcurrent Relays

The aim of the relay coordination is that protection systems detect and isolate the faulted part as fast and selective as possible. On the other hand, in order to reduce the fault clearing time, distance protection relays are usually equipped with pilot protection schemes. Such schemes can be considered in the distance and directional overcurrent relays (D&DOCRs) coordination to achieve faster ...

متن کامل

Providing A New Characteristic for Overcurrent Relays

This with the integration of distributed generation (DG) to meshed distribution systems, the operating time of the protective system becomes a major concern in order to avoid nuisance DG tripping. This paper proposes a new tripping characteristic for directional overcurrent relays (DOCRs) that can achieve a higher possible reduction of overall relays operating time in meshed distribution networ...

متن کامل

A Novel Objective Function for Directional Overcurrent Relays Coordination

Directional overcurrent relays (DOCRs) are widely used to protect power systems. For optimal coordination of DOCRs, several techniques have been proposed to solve this problem. A common way of optimal coordination of DOCRs is using evolutionary algorithms such as genetic algorithm (GA). In this paper, a novel strategy for DOCRs coordination is proposed. In the proposed strategy, a new objective...

متن کامل

هماهنگی بهینه رله های اضافه جریان جهتی در شبکه های توزیع با در نظر گرفتن پایداری گذرای منابع تولید پراکنده سنکرون

Integration of distributed generation (DG) into distribution networks causes some protection challenges, which can be solved by appropriate coordination of directional overcurrent relays. The optimal coordination of directional overcurrent relays is an important task to fulfill the protection requirements of the network. This paper presents an optimal coordination method for directional overcur...