Correlation between time and frequency domain polarisation measurements for transformer moisture assessment

نویسنده

  • T. K. Saha
چکیده

Preventative diagnosis and maintenance of transformers has become more popular in recent times in order to improve the reliability of electric power systems. A number of transformers have recently been tested using Return Voltage (RV) and Dielectric Dissipation Factor (tanδ) measurements in the time and frequency domain, respectively. This paper outlines a circuit model which describes the dielectric behaviour of the transformer insulation system and has been parameterised from the frequency domain data. This model was then used to simulate RV and Polarisation-Depolarisation current (PDC) results. Some recommendations about the diagnosis of the transformers have been proposed.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Improved Moisture Analysis of Power Transformers Using Dielectric Response Methods

This paper starts with a systematic benchmark test of the three commercialised dielectric diagnostic methods RVM (recovery voltage method), PDC (polarisation and depolarisation currents) and FDS (frequency domain spectroscopy), performed on a large transformer model. Starting from the explored strengths and weaknesses a more sophisticated instrument with corresponding software was developed. Th...

متن کامل

Separation of Ageing and Moisture Impacts on Transformer Insulation Degradation by Polarisation

This paper describes an accelerated ageing experiment of transformer oil/paper insulation with preset moisture levels. These samples were tested with return voltage and polarisation/depolarisation measurements. Molecular weight has also been measured with Gel Permeation Chromatography (GPC). Results suggested the impact of moisture on the ageing of oil/paper insulation. An attempt has been made...

متن کامل

Estimation of Moisture in Transformer Insulation Using Dielectric Frequency Response Analysis by Heuristic Algorithms

Transformers are one of the most valuable assets of power systems. Maintenance and condition assessment of transformers has become one of the concerns of researchers due to huge number of transformers has been approached to the end of their lifetimes. Transformer’s lifetime depends on the life of its insulation and the insulation’s life is strongly influenced by its moisture attraction as well....

متن کامل

Investigating the impacts of ageing and moisture on dielectric response of oil/paper insulation systems

The oil/paper insulation system in a transformer degrades under various chemical, thermal and electromechanical stresses during its operation. Dielectric response measurements like the Return Voltage Measurement (RVM) and Polarisation and Depolarisation Current (PDC) measurement are currently being used for condition assessment of the insulation. In the current research project, the ageing cond...

متن کامل

Review of Modern Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers

Cellulosic paper and oil insulation in a transformer degrade at higher operating temperatures. Degradation is accelerated in the presence of oxygen and moisture. Power transformers being expensive items need to be carefully monitored throughout its operation. Well established time-based maintenance and conservative replacement planning is not feasible in a current market driven electricity indu...