Moisture solubility for differently conditioned transformer oils - Dielectrics and Electrical Insulation, IEEE Transactions on [see also Electrical Insulation, IEEE
نویسندگان
چکیده
It is important to monitor the moisture content of transformer oil in a transformer. One parameter of particular interest is the moisture solubility of transformer oil. It has been reported that transformer oils under different conditions have different solubility. Measurements of solubility for four different types of conditioned oil are presented in this paper: fresh Shell Diala AX oil, lab-aged Shell Diala A oil, Texas Utility used transformer oil, and Ramapo Substation used transformer oil. To avoid the difficulty of achieving full saturation, this paper proposes an alternative method of measuring the moisture solubility in transformer oil using a relative humidity sensor. It utilizes the linearity between the relative humidity of the oil and the moisture content of the oil, to measure the solubility indirectly. The measured results of fresh oil, lab-aged oil, and the Texas Utility oil are very close, and only Ramapo oil shows different sensor response characteristics and solubility.
منابع مشابه
Optical, Electrical and Electromechanical Measurement Methodologies of Field, Charge and Polarizatio - Dielectrics and Electrical Insulation, IEEE Transactions on [see also Electrical Insulation, IEEE
A selective review is presented of the use of optical, electrical, and electromechanical measurement methodologies of the electric field, charge, conductivity, and permittivity in dielectrics. Kerr electro-optic measurements are presented to demonstrate how volume charge distributions can distort the electric field distribution :significantly and how the field and charge distributions depend on...
متن کاملA Feasible Solution to Distinguish the Transformer Winding Deformation from Insulation Characteristic Impacts on FRA Spectrum
Frequency Response Analysis (FRA) is popular technique which has been used since the last decade as a diagnostic method for transformers. However, accurate interpretation of FRA measurements is still challenging. Recent studies reveal that apart from winding deformation, FRA data can also be influenced by moisture variation in transformer paper insulation. Hence, a specific transformer’s model ...
متن کاملIEEE DEIS and Smart Grid
This paper describes the first steps taken by the IEEE Dielectrics and Electrical Insulation Society in defining their contributions to the Smart Grid concept. Keywords-Smart Grid, IEEE DEIS, diagnostics, monitoring, electrical insulation
متن کاملEstimation of Moisture in Transformer Insulation Using Dielectric Frequency Response Analysis by Heuristic Algorithms
Transformers are one of the most valuable assets of power systems. Maintenance and condition assessment of transformers has become one of the concerns of researchers due to huge number of transformers has been approached to the end of their lifetimes. Transformer’s lifetime depends on the life of its insulation and the insulation’s life is strongly influenced by its moisture attraction as well....
متن کاملFlow Electrification Measurements of Transformer Insulation using a Couette Flow Facility - Dielectrics and Electrical Insulation, IEEE Transactions on
A rotating cylindrical electrode apparatus, which provided cylindrical Couette flow, was used to simulate flow electrification in an electric power transformer. The apparatus had Shell Diala A transformer oil filling the annulus between coaxial cylindrical stainless steel electrodes that were either bare metal, or covered by a thin copper sheet and/or EHV-Weidmann HiVal pressboard insulation. E...
متن کامل