An alkaline approach to treating cooling towers for control of Legionella pneumophila.

نویسندگان

  • S J States
  • L F Conley
  • S G Towner
  • R S Wolford
  • T E Stephenson
  • A M McNamara
  • R M Wadowsky
  • R B Yee
چکیده

Earlier field and laboratory studies have shown that Legionella species survive and multiply in the pH range 5.5 to 9.2. Additionally, the technical feasibility of operating cooling towers at elevated alkalinities and pH has previously been documented by published guidelines. The guidelines indicate that these conditions facilitate corrosion control and favor chlorine persistence which enhances the effectiveness of continuous chlorination in biofouling control. This information suggests that control of Legionella species in cooling towers can be accomplished by operating the towers under alkaline conditions. To test this possibility, we collected water samples over a period of months from a hospital cooling tower. The samples were analyzed for a variety of chemical parameters. Subsamples were pasteurized and inoculated with non-agar-passaged Legionella pneumophila which had been maintained in tap water. Correlation of subsequent Legionella growth with corresponding pH and alkalinity values revealed statistically significant inverse associations. These data support the hypothesis that operating cooling towers outside of the optimal conditions for Legionella growth (e.g., at elevated alkalinities and a pH greater than 9) may be a useful approach to controlling growth in this habitat.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Failure of Legionella pneumophila sensitivities to predict culture results from disinfectant-treated air-conditioning cooling towers.

The disinfection of cooling towers based on manufacturers' treatment protocols, as employed in units installed at various public gathering places in Dallas, Tex. (hotels, municipal auditorium), and at the city health department, was evaluated for effectiveness in controlling Legionella pneumophila and compared with previous laboratory studies. In specimens collected in September and December, 1...

متن کامل

Isolation of Legionella pneumophila from hospital cooling towers in Johor, Malaysia.

Water-based cooling towers and their water supply at two hospitals in Johor were surveyed for the presence Legionella pneumophila. L. pneumophila were grown from 19 (76%) out of 25 collected water samples. One hospital cooling tower was contaminated with L. pneumophila serogroup 1.

متن کامل

Investigation and control of a cluster of cases of Legionnaires disease in western Sydney.

Three cases of Legionella pneumophila infection were identified in Sydney's west in November 1998. Epidemiological investigations identified an association with one workplace. Environmental sampling revealed that the cooling towers in the workplace, and at 2 other premises within a 1 km radius of the workplace, were positive for L. pneumophila serogroup 1 (LP1) which was indistinguishable from ...

متن کامل

First isolation of Legionella pneumophila in Sri Lanka.

OBJECTIVES To determine the presence of legionellae and species composition of the genus Legionella in Sri Lankan hotel cooling towers, and to determine the previous exposure of hotel workers to Legionella pneumophila. DESIGN Collection of water samples from 16 cooling towers of air conditioning plants from 7 representative hotels, and blood samples from hotel workers. SETTING Department of...

متن کامل

Outbreak of legionnaires' disease from a cooling water system in a power station.

In September and October 1981 six cases of pneumonia occurred among men working in a power station under construction. Three were identified as cases of legionella pneumonia and two others had serology suggestive of legionella infection. In a sample of 92 men from the site 10 had low levels of antibodies to legionella; a similar sample of men working on an adjacent site showed none with positiv...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:
  • Applied and environmental microbiology

دوره 53 8  شماره 

صفحات  -