Arc Motion and Gas Flow in Current Limiting Circuit Breakers Operating With a Low Contact Switching Velocity
نویسندگان
چکیده
Arc motion in low voltage (240 VAC) high current (10–10 A.) current limiting-circuit breakers is dominated by arc root mobility. The mobility is influenced by the gas flow and gas composition in the contact region, but there is little experimental data on these effects. New pressure and spectral data measurement during arc movement are presented using a flexible test apparatus and an arc imaging system. These measurements are used to investigate gas flow characteristics in the arc chamber. The chemical and physical phenomena occurring during the arc motion are discussed. The combination of optical and spectral data provides new insight into the arc motion. The influences of arc chamber material, contact material, and contact opening speed, are investigated, to improve arc control for a low contact opening velocity.
منابع مشابه
Investigating Characteristics of N2, CO2 and CF3I in Contrast to High Current Arcs in Circuit Breakers to Choose a Suitable Substitute for SF6
Specific and sensitive operation of circuit breakers makes an individual position for them in power networks. Circuit breakers are at the central gravity of variations and execution operations. Therefore, an optimum operation is the main reason to investigate about new gases to be used in MV and HV circuit breakers instead of SF6. The arc process has enormous complexity because of hydrodynamic ...
متن کاملMotion Studies of Cathode Roots in High Current Arcs using an Optical Fibre Array based Imaging System
This paper presents an integrated portable measurement system for the study of high speed and high temperature unsteady plasma flows such as those found in the vicinity of high current switching arcs. The system permits direct and non-intrusive measurement of arc light emission images with a capture rate of 1 million images per second (1MHz), and 8 bit intensity resolution. Novel software techn...
متن کاملFlexible Pulsed Dc- Source for Investigations of Hvdc Circuit Breaker Arc Resistance
The paper discusses the design of a flexible pulsed current source needed for experimental research of switching arcs in HVDC circuit breakers with passive resonance circuits. The source drives a current pulse from a pre-charged capacitor and forms it using an IGBT switch operated at 10kHz. The current source will be used to measure stationary and transient UIcharacteristics of switching arcs i...
متن کاملDynamical simulation of a Vacuum Switch with PSCAD
The switching behavior of vacuum switches (VS) is different to that of other circuit breakers. There are several effects which have to be taken into account, for example the current chopping, the dielectric strength of vacuum gap, the arc voltage, the quenching capability of high frequency currents, virtual current chopping and prestrikes. In some earlier investigations the characteristics of v...
متن کاملOptical fiber imaging for high speed plasma motion diagnostics: applied to low voltage circuit breakers.
An integrated portable measurement system is described for the study of high speed and high temperature unsteady plasma flows such as those found in the vicinity of high current switching arcs. An array of optical fibers allows the formation of low spatial resolution images, with a maximum capture rate of 1 x 10(6) images per second (1 MHz), with 8 bit intensity resolution. Novel software techn...
متن کامل