An Efficient Fault Locating Technique with Backup Protection Scheme Using Wide Area Measurement for Power System with Simultaneous Faults
نویسندگان
چکیده
This paper presents a synchronized phasor measurement-based wide-area backup protection scheme which uses the magnitude of sequence voltages of buses at a system protection centre to identify the faulted bus closest to the fault and faulted line. The technique is tested for various faults including simultaneous faults in various systems with interconnections. The scheme is found to be accurate and fast with today’s synchronized measurement technology. Analysis using simultaneous faults is a novel contribution in this paper. It is expected that this scheme will reduce the number of disastrous blackouts and improve the reliability and security of the power system. The required information is able to distinguish between balanced and unbalanced fault in the system. The study of new back up protection scheme is done on a WSCC-3 machine-9 bus system and an IEEE 14 bus test system. The data is simulated through EMTDC/PSCAD and MATLAB /SIMULINK softwares.
منابع مشابه
Simultaneous power sharing and protection against faults for DGs in microgrid with different loads
The LVRT (Low Voltage Ride Through) is the main characteristic of every power system in faulty conditions. When fault occurs, it is essential for power system such as microgrid to control the voltage and frequency normally. Naturally in fault status, the unbalanced voltage and current are inevitable, but with the aid of LVRT technique, microgrid can keep stability in main system parameters such...
متن کاملAn adaptive supervised wide-area backup protection scheme for transmission lines protection
Maloperation of conventional relays is becoming prevalent due to ever increase in complexity of conventional power grids. They are dominant during power system contingencies like power swing, load encroachment, voltage instability, unbalanced loading, etc. In these situations, adaptive supervised wide-area backup protection (ASWABP) plays a major role in enhancing the power system reliability. ...
متن کاملPower Differential based Wide Area Protection
Current differential based wide area protection (WAP) has recently been proposed as a technique to increase the reliability of protection systems. It increases system stability and can prevent large contingencies such as cascading outages and blackouts. This paper describes how power differential protection (PDP) can be used within a WAP and shows that the algorithm operates correctly for a...
متن کاملSmart Switching of Multi-terminal Hybrid DC Power Based on Load
A fault protection and location method for a dc bus micro grid system is presented in this paper. If a fault causes the dc bus to de-energize completely, it makes locating faults very difficult. The proposed algorithm can be implemented and executed by an intelligent electrical device for an individual node. The bus was segmented into overlapping nodes and links with circuit breakers (CBs) to i...
متن کاملProtection Scheme of Power Transformer Based on Time–Frequency Analysis and KSIR-SSVM
The aim of this paper is to extend a hybrid protection plan for Power Transformer (PT) based on MRA-KSIR-SSVM. This paper offers a new scheme for protection of power transformers to distinguish internal faults from inrush currents. Some significant characteristics of differential currents in the real PT operating circumstances are extracted. In this paper, Multi Resolution Analysis (MRA) is use...
متن کامل