The aim of this study was to identify the most effective disinfection protocol to reduce the presence of Legionella pneumophila in the water system of two Italian hospitals. From 2004 to 2009, 271 samplings of hot water were carried out in 11 hospital units to detect the presence of L. pneumophila. Additionally, water samples collected from one boiler outlet and the hot water recirculation were tested. From 2004 to 2009, L. pneumophila was present in 37% of the samples. Of these, 68.3% and 18.8% were positive for serogroups 2-14 and 1, respectively. Furthermore, 12.9% of the samples were positive for both serogroups. Finally, a maximal count of 10(4) CFU/L was measured in the most distal sites. To reduce L. pneumophila colonization, a two-year long hyperchlorination (2004-2006) was carried out. Moreover, from June 2005 until now, continuous maintenance of boilers and tanks, substitution of the shower heads and increase of the boiler outlet temperature to 60 °C were performed. All these treatments led to a marked reduction of L. pneumophila colonization in the short but not in the medium-long term. Only the use of chlorine dioxide led, after four years, to a reduction of the loads of L. pneumophila to values below 100 CFU/L. However, in the distal sites a persistent degree of colonization (maximum value 700 CFU/L, average 600 CFU/L) was observed probably due to the presence of L. pneumophila in the stagnant water in dead legs. In conclusion, data show that long-term chlorination of hot water sources together with carefully aimed maintenance of water pipes can lead to an effective reduction of L. pneumophila concentration in hospital water systems.
منابع مشابه
Role of environmental surveillance in determining the risk of hospital-acquired legionellosis: a national surveillance study with clinical correlations.
OBJECTIVE Hospital-acquired Legionella pneumonia has a fatality rate of 28%, and the source is the water distribution system. Two prevention strategies have been advocated. One approach to prevention is clinical surveillance for disease without routine environmental monitoring. Another approach recommends environmental monitoring even in the absence of known cases of Legionella pneumonia. We de...
متن کاملLegionella pneumophila Serogroup 1 in the Water Facilities of a Tertiary Healthcare Center, India
Proactive environmental surveillance for Legionella pneumophila in hospitals that treat immunocompromised patients is a useful strategy for preventing nosocomial Legionnaires' disease. We report the presence of L. pneumophila serogroup 1 in 15.2% of the water systems of our tertiary healthcare center, which should prompt health officials to formulate mitigation policies.
متن کاملInvestigation of Legionella Pneumophila bacteria in hospital water supply systems
Introduction: Legionella Pneumophila bacteria is known as one of the most important nosocomial infections and the most common cause of death in patients. This study was aimed to identify Legionella Pneumophila bacteria in hospital water supply systems. Material and Methods: This descriptive cross-sectional study was performed to identify Legionella pneumophila in hot and cold-water systems of i...
متن کاملEpidemiological investigation of a case of nosocomial Legionnaires' disease in Taiwan: implications for routine environmental surveillance.
An epidemiological investigation with Legionella and molecular subtyping was conducted to determine the source of a case of nosocomial Legionnaires' disease (LD) who was hospitalized in three hospitals within a month. Legionella pneumophila serogroup 3, an uncommon serogroup for infection, was isolated from the patient's sputum. Environmental surveillance revealed Legionella colonization in all...
متن کاملThe prevalence of environmentral colonization of Legionella in hospital water systems in Taiwan – a 20 hospital surveillance
Methods Twenty hospitals (Hospitals A to T) throughout Taiwan (8 in northern, 2 in central, 7 in southern, 2 in eastern Taiwan, and one in rural island) were cultured for Legionella. We followed the standardized protocol to perform environmental cultures using (1) water samples; (2) BCYE and DGVP culture media; (3) latex agglutination test (LAX) and direct fluorescent antibody (DFA) technique f...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید
ثبت ناماگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید
ورودعنوان ژورنال:
- Annali dell'Istituto superiore di sanita
دوره 46 3 شماره
صفحات -
تاریخ انتشار 2010