Synchronized Phasor Measurements in a Dual Layer Hybrid State Estimator
نویسندگان
چکیده
Original scientific paper The architecture of the proposed Dual Layer Hybrid State Estimator starts with the linear state estimator that only takes synchrophasors as inputs and calculates states of the buses with the deployed Phasor Measurement Units (PMUs) and their adjacent buses. These states are used to obtain the pseudomeasurements that are processed together with conventional SCADA measurements. As the relationship between the conventional measurements and the state variables is nonlinear, in this layer the iterative weighted least squares method is applied to estimate state of the complete power system. The developed formulation was tested on the IEEE systems as well as on the Croatian transmission power system model. The obtained results are compared with the classical solution that uses the conventional measurements and with another hybrid model. The hybrid state estimator based on the proposed architecture offers more accurate state estimation with enhanced filtering of measurements errors and with improved convergence capabilities.
منابع مشابه
Precise Synchronization of Phasor Measurements in Electric Power Systems
Phasors representing positive sequence voltages and currents ih a power network are the most important parameters i n several monitoring, control, and protection functions i n interconnected electric power networks. Recent advances in computer relaying have led to very efficient and accurate phasor measurement systems. When the phasors to be measured are separated by hundrea of miles, i t becom...
متن کاملAn Implementation of Two-stage Hybrid State Estimation with Limited Number of Pmu
State estimation is an important tool for power system supervision and control and the related applications. Based on the redundant measurements taken in the network, state estimation provides the most likely state of the power system. Conventional measurements were collected by the SCADA system and the measurement chain did not allow measurement synchronization. A disadvantage is that due to t...
متن کاملCritical Measurement Set with PMU for Hybrid State Estimation
This paper presents a method for designing minimal measurement set that include both Supervisory Control And Data Acquisition (SCADA) and Synchronized Phasor Measurements Units (SPMU) data for a Hybrid State Estimation (HSE). The optimal location of Phasor Measurement Units (PMU) is performed by Binary Integer Linear Programming (BILP). Among these PMUs, the highest priority indexed PMUs are se...
متن کاملA Two-Step Distribution System State Estimator with Grid Constraints and Mixed Measurements
In this work we study the problem of State Estimation (SE) in large-scale, 3-phase coupled, unbalanced distribution systems. More specifically, we address the problem of including mixed real-time measurements, synchronized and unsynchronized, from phasor measurement units and smart meters, into existing solutions. We propose a computationally efficient twostep method to update a prior solution ...
متن کاملA Framework for Phasor Measurement Placement in Hybrid State Estimation Via Gauss–Newton
In this paper, we study the placement of phasor measurement units (PMU) for enhancing hybrid state estimation via the traditional Gauss-Newton method, which uses measurements from both PMU devices and Supervisory Control and Data Acquisition (SCADA) systems. To compare the impact of PMU placements, we introduce a useful metric which accounts for three important requirements in power system stat...