Impact of GCSC on Measured Impedance by Distance Relay in the Presence of Single Phase to Earth Fault

نویسندگان

  • M. Zellagui
  • A. Chaghi
چکیده

This paper presents the impact study of GTO Controlled Series Capacitor (GCSC) parameters on measured impedance (Zseen) by MHO distance relays for single transmission line high voltage 220 kV in the presence of single phase to earth fault with fault resistance (RF). The study deals with a 220 kV single electrical transmission line of Eastern Algerian transmission networks at Group Sonelgaz (Algerian Company of Electrical and Gas) compensated by series Flexible AC Transmission System (FACTS) i.e. GCSC connected at midpoint of the transmission line. The transmitted active and reactive powers are controlled by three GCSC’s. The effects of maximum reactive power injected as well as injected maximum voltage by GCSC on distance relays measured impedance is treated. The simulations results investigate the effects of GCSC injected parameters: variable reactance (XGCSC), variable voltage (VGCSC) and reactive power injected (QGCSC) on measured resistance and reactance in the presence of earth fault with resistance fault varied between 5 to 50 Ω for three cases study. Keywords—GCSC Parameters, Transmission line, Earth fault, Symmetrical components, Distance protection, Measured impedance.

برای دانلود رایگان متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Effect of TCSR on Measured Impedance by Distance Protection in Presence Single Phase to Earth Fault

This paper presents the impact study of apparent reactance injected by series Flexible AC Transmission System (FACTS) i.e. Thyristor Controlled Series Reactor (TCSR) on the measured impedance of a 400 kV single electrical transmission line in the presence of phase to earth fault with fault resistance. The study deals with an electrical transmission line of Eastern Algerian transmission networks...

متن کامل

Effects of CT and VT Connection Point on Distance Protection of Transmission Lines with FACTS Devices

This paper presents the effects of instrument transformers connection points on the measured impedance by distance relays in the presence of Flexible Alternating Current Transmission System (FACTS) devices with series connected branch. Distance relay tripping characteristic itself depends on the power system structural conditions, pre-fault operational conditions, and especially the ground ...

متن کامل

A new interval approach for setting the distance relay zones to achieve perfect selectivity and maximum sensitivity

In this paper, an interval approach is presented to achieve perfect selectivity and maximum sensitivity in distance relay zones, considering uncertainties. For this purpose, first, the uncertainties affecting the settings of the three zones of a distance relay are discussed. Then, by using the Monte-Carlo simulation, the uncertainties are modelled and the impedances seen by the distance relay a...

متن کامل

A new interval approach for setting the distance relay zones to achieve perfect selectivity and maximum sensitivity

In this paper, an interval approach is presented to achieve perfect selectivity and maximum sensitivity in distance relay zones, considering uncertainties. For this purpose, first, the uncertainties affecting the settings of the three zones of a distance relay are discussed. Then, by using the Monte-Carlo simulation, the uncertainties are modelled and the impedances seen by the distance relay a...

متن کامل

A New Restricted Earth Fault Relay Based on Artificial Intelligence

The restricted earth fault (REF) relay is a type of differential protection which is used for detection of internal ground faults of power transformers. But, during external faults and transformer energization conditions, the probability of current transformer (CT) saturation increases. Thus, the spurious differential current due to CT saturation, can lead to REF relay maloperation. In this pap...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

عنوان ژورنال:

دوره   شماره 

صفحات  -