A Cycle Voltage Measurement Method and Application in Grounding Grids Fault Location
نویسندگان
چکیده
The corrosion of grounding grids can result in a grounding accident of a power system, and much attentions has been concentrated on the method used to detect a corrosion fault in a grounding grid, in which the methods of voltage measurement and magnetic field measurement are usually used. In this paper, a cycle voltage measurement method and L-curve regularization method are proposed to locate the faults in grounding grids. The L-curve method was used to select the appropriate regularization parameter, which can effectively balance the error and stability of the solution to the inverse problem. The uncertainty of the solution due to the ill-posed problem in the inverse problem has been well-solved. Experiments were conducted in a laboratory with two network types. In addition, a field experiment was carried out in a 110-kV substation. Both of the results showed that the method can effectively locate a branch fault with a single branch and multiple branches in the grounding grids.
منابع مشابه
Double phase fault location in microgrids with the presence of electric vehicles and Distributed parameters line model
Nowadays, renewable energy is increasingly used in smart grids and microgrids to reduce the use of fossil fuels and improve network efficiency. Like all power system devices, microgrids are subject to transient and steady-state faults, such as short circuits. These faults impair reliability and consumer dissatisfaction. To accurately, automatically, and economically determine the location of a ...
متن کاملFault Location in Active Distribution Networks Using Improved Whale Optimization Algorithm
To realize the self-healing concept of smart grids, an accurate and reliable fault locator is a prerequisite. This paper presents a new fault location method for active power distribution networks which is based on measured voltage sag and use of whale optimization algorithm (WOA). The fault induced voltage sag depends on the fault location and resistance. Therefore, the fault location can be f...
متن کاملDistribution Grid Fault Location Applying Transient Zero-mode Current
To aim at the puzzles on faults location in distribution grids, the paper analyzed the distributing characteristics of transient zero-mode currents as the faults occurred, with the aid of correlation theory, a new fault circuit-selection and fault-location method was proposed based on transient zero model current for power distribution grid faults. The method is based on such a fact that the RM...
متن کاملFault Location on Compensated Transmission Lines without Current Measurement
This paper presents a novel fault location method for series compensated transmission lines. It is established based on synchronized voltages sampling and Thevenin impedance from both ends of series compensated transmission line. The method is based on the use of phasor measurement units (PMU) technology which is aimed to be independent of current measurements, fault type, fault resistance, fau...
متن کاملمکانیابی خطا در خطوط انتقال با حضور محدودکننده جریان خطا
Fault location is an interesting subject in power grids. On the other hand, the application of fault current limiter (FCL) has been increasing in power network and causes some problems in operation of protection systems. This paper studies the application of FCL in power system and its effect on one-ended simple reactance fault location methods. In these methods, only voltages and currents of t...
متن کامل