Pilot-scale cooling tower to evaluate corrosion, scaling, and biofouling control strategies for cooling system makeup water.
نویسندگان
چکیده
Pilot-scale cooling towers can be used to evaluate corrosion, scaling, and biofouling control strategies when using particular cooling system makeup water and particular operating conditions. To study the potential for using a number of different impaired waters as makeup water, a pilot-scale system capable of generating 27,000 kJ∕h heat load and maintaining recirculating water flow with a Reynolds number of 1.92 × 10(4) was designed to study these critical processes under conditions that are similar to full-scale systems. The pilot-scale cooling tower was equipped with an automatic makeup water control system, automatic blowdown control system, semi-automatic biocide feeding system, and corrosion, scaling, and biofouling monitoring systems. Observed operational data revealed that the major operating parameters, including temperature change (6.6 °C), cycles of concentration (N = 4.6), water flow velocity (0.66 m∕s), and air mass velocity (3660 kg∕h m(2)), were controlled quite well for an extended period of time (up to 2 months). Overall, the performance of the pilot-scale cooling towers using treated municipal wastewater was shown to be suitable to study critical processes (corrosion, scaling, biofouling) and evaluate cooling water management strategies for makeup waters of complex quality.
منابع مشابه
Control of mineral scale deposition in cooling systems using secondary-treated municipal wastewater.
Secondary-treated municipal wastewater (MWW) is a promising alternative to freshwater as power plant cooling system makeup water, especially in arid regions. A prominent challenge for the successful use of MWW for cooling is potentially severe mineral deposition (scaling) on pipe surfaces. In this study, theoretical, laboratory, and field work was conducted to evaluate the mineral deposition po...
متن کاملPilot scale evaluation of mine water (MW) as a cooling medium
Sasol One abstracts large volumes of water from various sources, such as the Zuikerbosch & Vaal River for various applications including make-up to the cooling water systems. In an attempt to evaluate the use of underground MW as an alternative cooling medium, two pilot-scale cooling towers (CTs) were used. Data of five runs (3 weeks each) at different linear flow velocities (LFVs) and cycles o...
متن کاملA Low-cost, Safe, Effective Halogen Disinfectant for Cooling Towers
On-site, on-demand generation of MIOX mixed oxidant disinfecting solution provides several advantages for the cooling tower industry. These include excellent control of microbial populations even at the elevated pH typical of cooling tower waters, no negative impact on traditional scale and corrosion inhibitors, and environmentally friendly operating conditions. As an inherently safe technology...
متن کاملDesign and construction of a pilot scale heat exchanger-cooling tower system for scaling/deposition and inhibition studies
In this manuscript we present the design and construction of a pilot system that incorporates both a heat exchanger component and a cooling tower add-on. This prototype was constructed in order to simulate real industrial open recirculating cooling systems. Heat exchanger planning was realized using mass and energy balance. The application of mass balance was realized under permanent (static) c...
متن کاملInfluence of Chlorination and Choice of Materials on Fouling in Cooling Water System under Brackish Seawater Conditions
Cooling systems remove heat from components and industrial equipment. Water cooling, employing natural waters, is typically used for cooling large industrial facilities, such as power plants, factories or refineries. Due to moderate temperatures, cooling water cycles are susceptible to biofouling, inorganic fouling and scaling, which may reduce heat transfer and enhance corrosion. Hypochlorite ...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید
ثبت ناماگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید
ورودعنوان ژورنال:
- The Review of scientific instruments
دوره 83 2 شماره
صفحات -
تاریخ انتشار 2012