Besides compressor rotary speed and parameters of water flowing through gas cooler and evaporator, refrigerant charge amount and electronic expansion valve (EEV) opening are two important parameters that have significant effects on the performance of a transcritical CO2 heat pump system. In this study, the effects of refrigerant charge amount on the performance of a transcritical CO2 heat pump water heater were investigated experimentally at different EEV openings. An optimal coefficient of performance (COP) was found that corresponded to a specific refrigerant charge and a specific EEV opening. Based on the experiment, the COP peaked at charge of 1.8 kg when EEV opening was 40% of full opening. The heating capacity and the COP increased at first, reached peaks and then decreased with increase of charge amount. The COP decreased 14.95% as the CO2 charge amount was reduced by 22.2% from the optimal charge at 50% EEV opening. As EEV opening varied from 40% to 60% at the same charge amount, the heating capacity decreased more than 30%.
منابع مشابه
Experimental Investigation on the Influence of Refrigerant Charge on the Performance of Trans-critical CO2 Water-Water Heat Pump
For the environmentally aware, natural refrigerant such as CO2 is recommended and pursued by researchers for refrigerators. In this paper, a transcritical CO2 heat pump system was set up to investigate the influence of refrigerant charge on the performance of a small-sized heat pump water heater. The transcritical CO2 heat pump system was composed of a rotary compressor, a tube-in-tube evaporat...
متن کاملExperimental Study on the Heating Performance of a CO2 Heat Pump with Gas Injection
With the increasing of the environmental concerns, carbon dioxide (CO2) as an alternative refrigerant has been investigated intensively. In this study, the heating performance of a transcritical CO2 heat pump system with a twinrotary compressor was investigated. The transcritical CO2 heat pump with gas injection was tested by varying gas injection ratio and outdoor temperature at the optimum re...
متن کاملThe effects of improper refrigerant charge on the performance of a heat pump with an electronic expansion valve and capillary tube
For inverter heat pumps and multi-type heat pumps, conventional expansion devices such as capillary tubes, short tube orifices, and thermostatic expansion valves (TXVs) are being gradually replaced with electronic expansion valves (EEVs) because of the increasing focus on comfort and energy conservation. In this study, the effects of off-design refrigerant charge on the performance of a water-t...
متن کاملPerformance Evaluation of a Two-Stage Compression Heat Pump System With Refrigerant Charge and EEV Opening
متن کامل
Field Evaluation for Air-source Transcritical CO2 Heat Pump Water Heater with Optimal Pressure Control
Several optimal discharge pressure correlations for transcritical CO2 heat pump in literature have been discussed in this paper. Most of them are related to the ambient temperature, the evaporation temperature and the gas cooler outlet temperature. A revised optimal discharge pressure model as the function of ambient temperature and water outlet temperature is developed based on earlier experim...
متن کامل