Uhf Monitoring of Partial Discharge in Substation Equipment Using a Novel Multi-sensor Cable Loop
نویسنده
چکیده
This paper describes the development of a partial discharge measurement system that utilises a multiplexed approach to ultra-high-frequency monitoring on many pieces of equipment using a single cable loop connected to only two sampling channels. It is envisioned that the system could be used in partial discharge monitoring of medium voltage metal-enclosed switchgear, or several power transformers within a distribution substation. Conventionally, ultra-highfrequency monitoring of high voltage systems has used an array of sensors installed on each unit to facilitate PD location within the unit. The proposed system allows multiple small units to be monitored simultaneously, thus potentially spreading the cost of the measurement hardware across many pieces of equipment. This capability comes at the expense of limiting the partial discharge location capability to a particular item of plant rather than to a specific location within it.
منابع مشابه
Partial discharge signal detection using ultra high frequency method in high voltage power equipments: a review
Partial discharge (PD) can be detected using ultra high frequency (UHF) method to increase the detection threshold and to improve the performance of on-line measurement of PD in noise environment. The PD emitted energy as electromagnetic emission, acoustic emission and ozone and nitrous oxide gases. We can use this emitted energy to detected PD signal. The best method to detect PD in gas insula...
متن کاملA Novel Partial Discharge Localization Method in Substation Based on a Wireless UHF Sensor Array
Effective Partial Discharge (PD) localization can detect the insulation problems of the power equipment in a substation and improve the reliability of power systems. Typical Ultra-High Frequency (UHF) PD localization methods are mainly based on time difference information, which need a high sampling rate system. This paper proposes a novel PD localization method based on a received signal stren...
متن کاملApplication of HFCT and UHF Sensors in On-Line Partial Discharge Measurements for Insulation Diagnosis of High Voltage Equipment
Partial discharge (PD) measurements provide valuable information for assessing the condition of high voltage (HV) insulation systems, contributing to their quality assurance. Different PD measuring techniques have been developed in the last years specially designed to perform on-line measurements. Non-conventional PD methods operating in high frequency bands are usually used when this type of t...
متن کاملOn-site Portable Partial Discharge Detection Applied to Power Cables Using HFCT and UHF methods
Partial discharge (PD) events happen inside the power cables and cable terminations with the insulation degradation. The PD detection can effectively supply the information of cable status. According to the electrical and electromagnetic emission of PD activities, high-frequency transformer (HFCT) and ultrahigh-frequency (UHF) methods are employed to detect the PD signals. Besides, a portable P...
متن کاملPartial Discharge Monitoring of Power Transformers by UHF Sensors
The reliability of electrical energy networks depends on both, the quality and the reliability of its electrical equipment, e.g. power transformers. Local failures inside their insulation can lead to breakdowns and hence to high outage and penalty costs. Usually, power transformers are tested on partial discharge (PD) activity before commissioning. UHF PD monitoring can be used to prevent these...
متن کامل