Transformer Life Enhancement Using Dynamic Switching of Second Harmonic Feature in IEDs

نویسندگان

  • K. N. Dinesh Babu
  • P. K. Gargava
چکیده

Energization of a transformer results in sudden flow of current which is an effect of core magnetization. This current will be dominated by the presence of second harmonic, which in turn is used to segregate fault and inrush current, thus guaranteeing proper operation of the relay. This additional security in the relay sometimes obstructs or delays differential protection in a specific scenario, when the 2nd harmonic content was present during a genuine fault. This kind of scenario can result in isolation of the transformer by Buchholz and pressure release valve (PRV) protection, which is acted when fault creates more damage in transformer. Such delays involve a huge impact on the insulation failure, and chances of repairing or rectifying fault of problem at site become very dismal. Sometimes this delay can cause fire in the transformer, and this situation becomes havoc for a sub-station. Such occurrences have been observed in field also when differential relay operation was delayed by 10-15 ms by second harmonic blocking in some specific conditions. These incidences have led to the need for an alternative solution to eradicate such unwarranted delay in operation in future. Modern numerical relay, called as intelligent electronic device (IED), is embedded with advanced protection features which permit higher flexibility and better provisions for tuning of protection logic and settings. Such flexibility in transformer protection IEDs, enables incorporation of alternative methods such as dynamic switching of second harmonic feature for blocking the differential protection with additional security. The analysis and precautionary measures carried out in this case, have been simulated and discussed in this paper to ensure that similar solutions can be adopted to inhibit analogous issues in future. Keywords—Differential protection, intelligent electronic device (IED), 2 harmonic, inrush inhibit.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Dynamic Harmonic Analysis of Long Term over Voltages Based on Time Varying Fourier series in Extended Harmonic Domain

Harmonics have become an important issue in modern power systems. The widespread penetration of non-linear loads to emerging power systems has turned power quality analysis into an important operation issue under both steady state and transient conditions. This paper employs an Extended Harmonic Domain (EHD) based framework for dynamic analysis of long term analysis over voltages during the tra...

متن کامل

Harmonic Reduction Technique Using Flying Capacitor Based Z Source Inverter for a DVR

The Dynamic Voltage Restorer (DVR) is a commercially available, popular device to eliminate voltage sags and swells in the distribution lines. Its basic function is to inject the voltage difference (difference between the pre-sag and sag voltage) to the power line and maintains the pre-sag voltage condition in the load side. The efficiency of the DVR depends on the performance of the efficiency...

متن کامل

Investigation and Control of Unstable Chaotic Behavior Using of Chaos Theory in Two Electrical Power Systems: 1-Buck Converter2- Power Transformer

This paper consist of two sections: control and stabilizing approach for chaotic behaviour of converter is introduced in first section of this paper for the removal of harmonic caused by the chaotic behaviour in current converter. For this work, a Time- Delayed Feedback Controller (TDFC) control method for stability chaotic behaviour of buck converter for switching courses in current control mo...

متن کامل

Dynamic Harmonic Modeling and Analysis of VSC-HVDC Systems

Harmonics have become an important issue in modern power systems. The widespread penetration of non-linear loads to emerging power systems has turned power quality analysis into an important operation issue under both steady state and transient conditions. This paper employs a Dynamic Harmonic Domain (DHD) based framework for dynamic harmonic analysis of VSC-HVDC systems. These systems are wide...

متن کامل

Dynamic Compensation of Electrical Power Systems Using Multilevel Voltage Source Inverter

A New Static Var Generator (SVG), using cascaded full-bridge inverters (FBI) with binary output levels and the parallel connections of two cascaded inverters by means of current sharing reactor in each phases is introduced. The new M-level inverter, where M is 2n+2 - 3, consists of only 2n single-phase full bridges for each phases. The proposed technique not only increases the current capacity ...