Electrical Structure-Based PMU Placement in Electric Power Systems
نویسنده
چکیده
Recent work on complex networks compared the topological and electrical structures of the power grid, taking into account the underlying physical laws that govern the electrical connectivity between various components in the network. A distance metric, namely, resistance distance was introduced to provide a more comprehensive description of interconnections in power systems compared with the topological structure, which is based only on geographic connections between network components. Motivated by these studies, in this paper we revisit the phasor measurement unit (PMU) placement problem by deriving the connectivity matrix of the network using resistance distances between buses in the grid, and use it in the integer program formulations for several standard IEEE bus systems. The main result of this paper is rather discouraging: more number of PMUs are required, compared with those obtained using the topological structure, to meet the desired objective of complete network observability without zero injection measurements. However, in light of recent advances in the electrical structure of the grid, our study provides a more realistic perspective of PMU placement in power systems. By further exploring the connectivity matrix derived using the electrical structure, we devise a procedure to solve the placement problem without resorting to linear programming.
منابع مشابه
PMU Placement Methods in Power Systems based on Evolutionary Algorithms and GPS Receiver
In this paper, optimal placement of Phasor Measurement Unit (PMU) using Global Positioning System (GPS) is discussed. Ant Colony Optimization (ACO), Simulated Annealing (SA), Particle Swarm Optimization (PSO) and Genetic Algorithm (GA) are used for this problem. Pheromone evaporation coefficient and the probability of moving from state x to state y by ant are introduced into the ACO. The modifi...
متن کاملOptimal PMU Placement Considering with HVDC Links and Their Voltage Stability Requirements
In wide area measurement systems, PMUs are the main component measuring real time synchronized data from different buses. Installation of PMUs at all buses is a primary way to provide full observability of the power network. However, it is not practical in real networks due to the relatively expensive cost of PMUs and other technical limitations. Optimal PMU Placement (OPP) is an optimization p...
متن کاملAn Electrical Structure-Based Approach to PMU Placement in the Electric Power Grid
The phasor measurement unit (PMU) placement problem is revisited by taking into account a stronger characterization of the electrical connectedness between various buses in the grid. To facilitate this study, the placement problem is approached from the perspective of the electrical structure which, unlike previous work on PMU placement, accounts for the sensitivity between power injections and...
متن کاملA Unifying Framework for the Electrical Structure-Based Approach to PMU Placement in Electric Power Systems
The electrical structure of the power grid is utilized to address the phasor measurement unit (PMU) placement problem. First, we derive the connectivity matrix of the network using the resistance distance metric and employ it in the linear program formulation to obtain the optimal number of PMUs, for complete network observability without zero injection measurements. This approach was developed...
متن کاملPresenting a New Method Based on Branch Placement for Optimal Placement of Phasor Measurement Units
In this paper, a new method based on branch placement for the optimal positioning of Phasor Measurement Units (PMUs) in power systems is proposed. In this method, the PMUs are in type of single-channel and are installed at the beginning of the branches. Therefore, they are able to measure the bus voltages. Also, the installation of the PMUs on the branches increases the security of observabilit...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید
ثبت ناماگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید
ورودعنوان ژورنال:
- CoRR
دوره abs/1309.1300 شماره
صفحات -
تاریخ انتشار 2013