Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance
نویسندگان
چکیده
An experimental investigation was implemented to determine the capacity degradation due to non-uniform refrigerant and air flow distributions, and to assess the potential to recover the lost capacity via controlling refrigerant distribution between individual refrigerant circuits. The tests were performed on a three-circuit, threedepth-row, finned-tube evaporator. Refrigerant inlet quality, exit saturation temperature, and exit superheats for the individual circuits were controlled. The study showed that capacity degradation due to refrigerant maldistribution can be as much as 30 %, even when the overall evaporator superheat is kept at the target 5.6 oC. Experimental data indicate that part of this capacity degradation was caused by the internal heat transfer within the evaporator assembly. For the coil and air maldistributions studied, the maximum capacity degradation was found to be 8.7 %. A 4.0% capacity recovery was obtained by controlling refrigerant distribution to obtain the target 5.6 oC at each circuit exit.
منابع مشابه
Design and Experimentation of Roll Bond Evaporator for Room Air Conditioner with R-22 as Refrigerant
The world is looking towards producing products which consume less power without compromising on quality of life. The increase in use of refrigeration and air conditioning appliances are contributing to global warming. The world wide temperatures are shooting up at an increasing rate. This paper presents a design of roll bond evaporator as the heat exchanger to provide cooling in room air condi...
متن کاملAn Optimized Design of Finned-Tube Evaporators Using the Learnable Evolution Model
Optimizing the refrigerant circuitry for a finned-tube evaporator is a daunting task for traditional exhaustive search techniques due to the extremely large number of circuitry possibilities. For this reason, more intelligent search techniques are needed. This paper presents and evaluates a novel optimization system, called ISHED1 (Intelligent System for Heat Exchanger Design). This system uses...
متن کاملEffect of Coil Geometry on Frost-Free Finned-Tube Evaporator Performance
This paper outlines a mathematical modelling approach to predict the steady-state behaviour of finned-coil evaporators. The model was built taking three domains into account: (i) refrigerant flow inside the coil; (ii) heat transfer through the walls; and (iii) air flow through the finned-coil array. The equations were obtained from the mass, momentum and energy conservation principles, mathemat...
متن کاملCapability Optimization of refrigerant Circuitry for a Finned Tube Heat Exchanger-A Theoretical Review
Increased concerns about climate change and day by day increment in energy cost has created the importance of Refrigeration & Air Conditioning system with high COP. COP of a Vapour Compression Refrigeration system is mainly influenced by the effectiveness of the Heat Exchanger being Employed. Optimization in the design of Heat Exchanger is highly desirable to improve their effectiveness and red...
متن کاملPerformance of a finned-tube evaporator optimized for different refrigerants and its effect on system efficiency
This paper presents a comparable evaluation of R600a (isobutane), R290 (propane), R134a, R22, R410A, and R32 in an optimized finned-tube evaporator, and analyzes the impact of evaporator effects on the system coefficient of performance (COP). The study relied on a detailed evaporator model derived from NIST’s EVAP-COND simulation package and used the ISHED1 scheme employing a non-Darwinian lear...