Detection and Position Location of Partial Discharges in Transformers Using Fiber Optic Sensors
نویسنده
چکیده
Power transformers are one of the most important components in the electrical energy network. Extending transformer life is very economically valuable due to power outage. Therefore the development of instruments to monitor the transformer condition is of great interest. Detection of partial discharges (PDs) in power transformers is an effective diagnostic because it may reveal and quantify an important aging factor and provide information on the condition of the transformer. However, partial discharge diagnostics are still not effectively used for online monitoring of transformers because of the complexity of PD measurements and difficulties of discriminating of PDs and other noise sources. This thesis presents a further study of detection and location of partial discharges in power transformers based on previous work conducted at the Center for Photonics Technology (CPT) at Virginia Tech. The detection and positioning system consists of multiple extrinsic Fabry-Parot interferometric (EFPI) fiber acoustic sensors which can survive the harsh environment of oil-filled transformers. This thesis work is focused on optimal arrangement of multiple sensors to monitor and locate PD activities in a power transformer. This includes the following aspects. First, the sensor design requirements are discussed in order to successfully detect and accurately position the PD sources. In the following sections, Finite Element Method (FEM) is used to model the EFPI sensor fabricated at CPT. Experiments were conducted to measure the angular dependence of the frequency response of the sensor. It is shown that within the range of ±45o incident angles, the sensitivity varies by 3-5dB. Finally, the thesis demonstrates a PD positioning experiment in a 500 gallon water tank (R × H = 74’’ × 30’’ cylinder) using a hyperbolic positioning algorithm and time difference of arrival (TDOA). Finally we demonstrated that 100% of the positioning data is bounded by a 22.7×4.1×5.3 mm cube, with a sensing range of 810 mm using the leading edge method
منابع مشابه
Detection and wavelet analysis of partial discharges using an optical fibre interferometric sensor for high-power transformers
The main problem in power transformers is the degradation of the isolation, and partial discharges are a major contribution to this shortcoming. Partial discharges inside mediumand high-power transformers generate ultrasonic pressure waves which are usually detected by using acoustic piezoelectric sensors placed outside the transformers. In this paper we describe an optical fibre interferometri...
متن کاملA Fiber Optic PD Sensor Using a Balanced Sagnac Interferometer and an EDFA-Based DOP Tunable Fiber Ring Laser
A novel fiber-optic acoustic sensor using an erbium-doped fiber amplifier (EDFA)-based fiber ring laser and a balanced Sagnac interferometer for acoustic sensing of the partial discharge (PD) in power transformers is proposed and demonstrated. As a technical background, an experimental investigation on how the variations of the fiber birefringence affect the sensor performances was carried out,...
متن کاملAn Optic Fiber Sensor for Partial Discharge Acoustic Detection
AN OPTIC FIBER SENSOR FOR PARTIAL DISCHARGE ACOUSTIC DETECTION by Xiaodong Wang Partial discharge (PD) is a very common problem in operating power transformers and is one of the factors that could lead to failure of power transformers, leading to power outage and expensive repairs. The acoustic wave induced by PD can be measured and used for monitoring, diagnosing, and locating potential failur...
متن کاملAn ultra-sensitive optical MEMS sensor for partial discharge detection
A diaphragm-based interferometric fiber optical microelectromechanical system sensor with high sensitivity is designed and tested for on-line detection of the acoustic waves generated by partial discharges (PD) inside high-voltage power transformers. In principle, the sensor is made according to Fabry Perot interference, which is placed on a micro-machined rectangular silicon membrane as a pres...
متن کاملPartial Discharge Monitoring in Power Transformers Using Low-Cost Piezoelectric Sensors
Power transformers are crucial in an electric power system. Failures in transformers can affect the quality and cause interruptions in the power supply. Partial discharges are a phenomenon that can cause failures in the transformers if not properly monitored. Typically, the monitoring requires high-cost corrective maintenance or even interruptions of the power system. Therefore, the development...