Analysis of partial discharge Ultrasonic wave characteristic on typical Defects in GIS

نویسندگان

  • Jing Gang YANG
  • Wen SHI
  • Hong Tao LI
  • Bin GONG
  • Wei Yi JIANG
چکیده

For analyzing partial discharge ultrasonic wave characteristic on typical defects in SF6 gas insulation switchgear (GIS), a 110 kV GIS was taken as an object to design and simulate the typical partial discharge models in GIS There are point electrode model on bus and cavity of GIS, floating electrode model, air interstice model in insulator, metal particle and iron core electromagnetic shock models. PD signals on different defects were thus detected with the ultrasonic method The experimental results indicated that the ultrasonic signals of different defects showed different characteristics in waveform, amplitude and phase resolved partial discharge chart, which is helpful in PD pattern recognition for GIS

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Characteristic Analysis of Partial Discharge Detection in GIS

Abstract Partial discharge (PD) detection is a valuable method for the estimation of GIS condition, and the PD mapping is benefit for GIS defects identification. To investigate the PD characteristic of the GIS model, this paper simulates different PD maps of various fault simulations, and the characteristics of PD map is acquired by the pulse amplitude, phase and the discharge density to identi...

متن کامل

The Comprehensive Study Based on Ultrasonic and X-ray Visual Technology for GIS Equipment Detection

For lack of the visualization of the ultrasonic detection method of partial discharge (PD), the ultrasonic detection technology combined with the X-ray visual detection method (UXV) is proposed. The method can conduct qualitative analysis accurately and conduct reliable positioning diagnosis to the internal insulation defects of GIS, and while it could make up the blindness of the X-ray visual ...

متن کامل

Partial Discharge Diagnosis on GIS Based on Envelope Detection

In order to detect and identify the defects on GIS, the ultra-high frequency envelope detection circuit and high-speed data acquisition system was designed, and the tests of five typical defects for GIS were made in the laboratory and the envelope signal was acquired based on Ultra-high frequency (UHF) envelop detection circuit. And wavelet denoising technique was used to reduce the white noise...

متن کامل

Correlation Characteristics Comparison of SF6 Decomposition versus Gas Pressure under Negative DC Partial Discharge Initiated by Two Typical Defects

Aimed to clarify the correlation characteristics between the internal partial discharge (PD) in negative direct current (DC) gas insulated system (GIS) and gas pressure initiated by two typical defects (i.e., free-metal particles and metal protrusion), this study on PD decomposition of sulfur hexafluoride (SF6) was investigated under different pressures on the basis of constructing a SF6 decomp...

متن کامل

Ultrasonic guided waves reflection from simple dent in pipe for defect rate estimation and parameters determination of axisymmetric wave generation source

In this paper, the reflection of ultrasonic guided waves from simple dent in pipes has been investigated using finite element method and the relationship between reflection coefficient of these waves and deformation rate has been determined. Also, the effect of the parameters of wave generation source on the generated wave field has been investigated using normal modes expansion method. At firs...