Reliability modeling and data analysis of vacuum circuit breaker subject to random shocks
نویسندگان
چکیده
The electrical substation components are often subject to degradation due to over-voltage or over-current, caused by a short circuit or a lightning. A particular interest is given to the circuit breaker, regarding the importance of its function and its dangerous failure. This component degrades gradually due to the use, and it is also subject to the shock process resulted from the stress of isolating the fault when a short circuit occurs in the system. In this paper, based on failure mechanisms developments, the wear out of the circuit breaker contacts is modeled. The aim of this work is to evaluate its reliability and consequently its residual lifetime. The shock process is based on two random variables such as: the arrival of shocks and their magnitudes. The arrival of shocks was modeled using homogeneous Poisson process (HPP). By simulation, the dates of short-circuit arrivals were generated accompanied with their magnitudes. The same principle of simulation is applied to the amount of cumulative wear out contacts. The objective reached is to find the formulation of the wear function depending on the number of solicitations of the circuit breaker. Keywords—reliability, short-circuit, models of shocks.
منابع مشابه
Reliability-Based Preventive Maintenance of Oil Circuit Breaker subject to Competing Failure Processes
This paper investigates technical and organizational tools to improve performances of a multi-state degraded system subject to multiple competing failure processes. The competing failure processes treated in this paper are oil insulating aging and electrical contacts wear out of high voltage oil circuit breaker. To degradation processes, is associated random shocks process highlighted by the st...
متن کاملInvestigating Impacts of Sustainable Repair Time and Circuit Breaker Model on Meshed Distribution Networks Reliability Assessment
Generally, the failure rate and the repair time of system components are constant parameters in reliability assessment of electric distribution systems. A failure of component is resulted from failing in the operation or overloading. In addition, there exist cases where, the repair times of components are small and tolerable from customer point of view. Thus, tolerable repair times may be overl...
متن کاملAnalysis of Electric Field and Polarization of SF6 Circuit Breaker to Approach a Suitable Structure
Abstract: The application of electric field theory to widely different aspects of electrical insulation has led to more understanding the phenomena. Electric fields may be considered as the main reason for insulation failure. The purpose of this paper is to modify importance of analyzing electric field in insulation design. The SF6 circuit breaker is chosen as case study that encounters cri...
متن کاملOnline Monitoring System Design of Intelligent Circuit Breaker Based on DSP and ARM
In order to accurately analyze the dynamic characteristics of the vacuum circuit breaker, a dual-core master-slave processor structure for online monitoring system based on DSP and ARM is proposed. This structure consists of host computer, lower computer and signal processing modules. The lower computer uses DSP as the core, which completes acquisition and data preprocessing of circuit breaker’...
متن کاملA Model-Based Fault Detection Framework for Vacuum Circuit Breaker by Trip Coil Analysis
Vacuum circuit breaker becomes more and more complicated, integrated, high-speed and intellectualized. To insure vacuum circuit breaker in its good conditions, the function of fault diagnosis gets more important than before in the process of repairing. This paper is addressed a modelbased fault detection framework for vacuum circuit breaker by trip coil analysis. At first, the electromagnetic m...
متن کامل