Induced Overvoltages on the SF6 Substation Enclosure Caused by Switching
نویسندگان
چکیده
Abstract – This paper investigates overvoltages on the SF6 substation enclosure caused by the switching operation of the interrupter. The paper analyzes the amplitude and the overvoltage duration on the substation enclosure. Switching overvoltages take part in the everyday drive of HV substations and constitute an undesired phenomenon that may often, beside transient disturbances, lead to undesired cases as well. Electrical discharge in the SF6 gas dielectric, caused by very fast overvoltages, spreads from the place of its occurrence towards all directions within the substation, which on discontinuities (e.g. connection bushings, cable bushings) also includes spreading onto the external side of the enclosure and earthed parts of the substation. Such overvoltages are characterized by a very high frequency for which even low inductances represent very high impedances. This paper is focused on simulation options of the transient connection GIS-overhead line in simulation software. Literature sources provide a fine description of the physical background of the observed phenomena. However, it is difficult to find a model presentation in certain software. Due to this fact, this paper shows possible ways of simulating the GIS-air connection with objects in ATP software. Induced Overvoltages on the SF6 Substation Enclosure Caused by Switching
منابع مشابه
Mitigation of Transient Overvoltages Generated Due to Switching Operations and Lightning in Gas-insulated Substation (GIS) Without Extra Limiter
Gas-insulated substations (GIS) have different specifications in proportion to air-insulated substations. Transformer failures related to lightning and switching are often reported in the gas insulated substation (GIS). This problem is the voltage magnifications due to reflections of switching and lightning surges at various junctions within the GIS. thereby overvoltages in GIS are more importa...
متن کاملSensitivity Assessment of Lightning Protection Device Aging Effect on Distribution Substation Insulation
Insufficient electrical endurance of equipment and insulation failure against overvoltage is one of the most effective reasons for failure the power line. Lightening, switching or other disruptive parameters can cause line outage or distribution substation failure. There are different devices used to improve the safety, reliability, and power quality of the system. Surge arresters are one of t...
متن کاملPerformance of Surge Arrester to Multiple Lightning Strokes on Nearby Distribution Transformer
Overhead distribution lines are prone to lightning overvoltages due to their configurations and characteristics. Metal Oxide Varistor (MOVs) arresters for many years have proven to be more advantageous than others arresters in lightning surge protection; therefore it is worthwhile to continually assess the behavior and performance of these arresters to different kind of overvoltages caused by l...
متن کاملOn The Processing Of The Recorded Data For The SF6 Circuit Breakers From The Transformation Substation 110/20/6kV Craiova South
The assurance of the reliability for the transformation substations is one of primary goals of the manufacturers and distributors of electricity. Therefore, a proper monitoring and maintenance program is required. The circuit breaker is a complex device, subject to the thermal and mechanical stresses during the normal or fault currents switching. The substations are frequently equipped with SF6...
متن کاملRadial Basis Function Neural Network Application to Power System Restoration Studies
One of the most important issues in power system restoration is overvoltages caused by transformer switching. These overvoltages might damage some equipment and delay power system restoration. This paper presents a radial basis function neural network (RBFNN) to study transformer switching overvoltages. To achieve good generalization capability for developed RBFNN, equivalent parameters of the ...