Insulation coordination of MV cables against lightning - induced overvoltages generated by LEMP - coupled overhead lines
نویسنده
چکیده
-The paper deals with the stresses of cable insulations due to lightning induced overvoltages for the case of distribution networks composed by MV overhead lines and buried cables. We are here interested only in the conditional probability of the cable breakdown in absence of line flashovers, which means that flashovers along the overhead line are disregarded. We illustrate a procedure based on the application of the Monte Carlo method and on a simulation tool for the accurate computation of lightning-induced voltages on an overhead line, namely the LIOV code. A frequency dependent parameter cable model is used for the calculation of the overvoltages stressing the cable insulation, which is assumed not to be illuminated by LEMP. We associate to each calculated overvoltage a breakdown probability for the cable, by using experimentally obtained probabilistic distributions of the breakdown voltages of the cable insulation for different families of voltage wave shapes. These probabilities, together with the expected number and characteristics of the lightning events, allow us to infer the yearly number of expected failure events in the above assumptions. The breakdown behavior of extruded cable insulation is represented by a 2-parameter Weibull distribution obtained from experimental tests on cable models, manufactured with the same materials and same technologies of real cables, by applying the well-known statistical “enlargement law”.
منابع مشابه
Lightning Protection of Overhead Power Distribution Lines
Distribution lines are often located in areas with high ground flash densities, being therefore subject to lightning-caused power interruptions. This paper presents an overview of the various types of lightning overvoltages that can arise on overhead power distribution networks, as well as typical voltage waveforms. The effectivenesses of the most important methods for mitigating such overvolta...
متن کاملThe effect of grounding system modeling on lightning-related studies of transmission lines
Un-accurate modeling of power system may cause to under or over-design the insulation, which in turn, leads to increase in the investment and/or maintenance cost of the network protection against lightning overvoltages. The grounding system is an effective parameter on the magnitude of the lightning overvoltages and insulation coordination of high voltage transmission lines (TLs). This paper pr...
متن کاملSimulation of Lightning Overvoltages in Electrical Power Systems
Lightning strikes to overhead transmission lines cause travelling waves which propagate along the overhead line and enter substations where they cause overvoltages which can pose a risk to any items of equipment connected, such as cables or transformers. With the use of metal-oxide arresters, these overvoltages are reduced to values which, taking into account an adequate safety margin, are belo...
متن کاملتخمین عملکرد خطوط و ریسک عایقی ناشی از ضربات مستقیم صاعقه با استفاده از روش ترکیبی جدید مبتنی بر روش مونت کارلو
This paper presents a new method, based on analytical relations and Monte Carlo simulation for calculating the lightning performance of overhead lines caused by direct strokes. The aim of the work is to reduce the computing time together with retaining enough accuracy to estimate the line lightning performance and performing the risk analysis of power networks. In the proposed method, some modi...
متن کاملSensitivity Assessment of Lightning Protection Device Aging Effect on Distribution Substation Insulation
Insufficient electrical endurance of equipment and insulation failure against overvoltage is one of the most effective reasons for failure the power line. Lightening, switching or other disruptive parameters can cause line outage or distribution substation failure. There are different devices used to improve the safety, reliability, and power quality of the system. Surge arresters are one of t...