A Signal Processing Technique for PD Detection and Localization in Power Transformer Winding
نویسنده
چکیده
Precise detection and localization of faults in power transformer windings for ultimate protection is the key issue. The insulation quality in windings majorly determines the enduring transformers function. Achieving as accurate and efficient detection method of partial discharge (PD) in transformer windings is challenging. The occurrence of PD being primarily responsible for the transformers failure its detection is considered as preventive measure to avoid large-scale economic losses. This paper briefly overviews the salient features of the conventional acoustic and travelling wave methods those electrically determine the dominant capacitive region in the frequency domain. We propose a technique which is based on the PD signal detection and the measurement of the characteristics transfer functions in the frequency domain. A distributed circuit transformer model with eight sections is developed and simulated via Matlab code. PD signals analogous to sources in various locations are injected at different points within the transformer windings. The PD source positions are determined in terms of the number of turns from the line-end. The determination of PD locations on the basis of zero frequency differences is demonstrated. Our method significantly improved the accuracy to identify the PD location. The limitations associated with the appearance of noise and the frequency range for detection is overcome. The occurrence of crests and troughs in the frequency spectra are used to locate the source of PD activity in transformer windings.
منابع مشابه
Evaluating the Improvement of Partial Discharge Localization Accuracy Using Frequency Response Assurance Criterion
Partial Discharge (PD) is the most important source of insulation degradation in power transformers. In order to prevent catastrophic failures in transformers, PDs need to be located as soon as possible so that maintenance measures can be taken in time. Due to the structural complexity of windings, locating the PD source inside a transformer winding is not a simple task. In this paper, the effi...
متن کاملمدلسازی سیم پیچ ترانسفورماتورهای قدرت با استفاده از مدل خط انتقال چند سیمه بمنظور مکانیابی تخلیه جزئی
In this paper Multi conductor transmission line model (MTLM) was used for partial discharge (PD) localization in power transformers’ windings. The parameters of the model were computed considering practical issues of power transformer design. To decrease computational complexity of the model, two methods for calculation of model parameters were studied and the most suitable method was cho...
متن کاملA Method for Extracting Partial Discharge Signals in Transformer Winding with Wavelet Analysis
In this paper a method for extracting Partial Discharge (PD) signals is introduced, which is implemented for evaluating electrical measured partial discharges on a 66 kV / 25 MVA fully interleaved winding of a power transformer. Applying wavelet transform to a signal produces a wavelet detail coefficient distribution throughout the time-scale, which depends on the mother wavelet chosen. This me...
متن کاملEfficiency Improvement of the Flyback Converter Based on High Frequency Transformer Winding Rearrangement
In this paper, a novel method for loss reduction and efficiency optimization of the high frequency flyback transformers is proposed based on rearrangement of the windings. According to detailed analysis of the high frequency flyback transformer using FEM technique, a novel and simple approach for its design improvement and loss reduction is introduced. It is shown that leakage flux scattering i...
متن کاملImproved Detection Sensitivity with Combined WPT and HHT for Power Transformer Winding Deformation Analysis
The success of health monitoring and condition assessment of power transformers based on winding current signature analysis lies on proper extraction of features. The extraction of features in turn depends on appropriate signal processing methods. Fourier based signal analysis provides only frequency information and also suitable only for stationary signals. In this paper we present a combined ...