Transformer Models for Detection of Incipient Internal Winding Faults

نویسندگان

  • Hang Wang
  • Peter Palmer-Buckle
  • Karen L. Butler
چکیده

A method of modeling internal turn-to-earth and turn-toturn faults in distribution transformer is discussed in this paper. The models are entirely compatible with the Alternative Transients Program(ATP). The simulation of the faults is based on known leakage factors between the various coils of the transformer. These leakage factors are evaluated by using a simple method implemented in this paper. A fault between any turn and earth and between any two turns on either winding of a single-phase transformer can be simulated using this method. In this paper, the terminal behavior of a test transformer is studied through the simulation of a simple system in ATP. When faults are introduced at various locations in the transformer primary and secondary windings, the terminal voltages and currents behaved as expected.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Transformer Internal Incipient Fault Simulations

Transformer fault detection and diagnosis is becoming more important due to the restructuring of the electric power industry. In this era of deregulation, loading transformers to their optimum capacity is becoming normal practice, which in turn applies high stresses on the insulation of the transformers and increases the probability of occurrence of internal incipient faults. Such faults can le...

متن کامل

Inter-Turn Fault Detection in Power transformer Using Wavelets

Detection and removal of incipient faults in power transformer winding is essential because minor faults may develop and lead to major faults and finally irretrievable damages occur. This research article presenta a new, simple and incipient fault detection technique, which is based on symmetrical component approach. Using this protection technique, it is possible to detect minor turn-to-turn f...

متن کامل

Transformer Internal Winding Faults Diagnosis Methods: A Review

A transformer is a vital component in any power system network and its catastrophic failure may cause disturbance in the proper operation of electrical power system network. Therefore, it requires continuous monitoring and diagnostics of its operation. This paper presents the several on-line and off-line techniques related with internal winding fault detection in transformers. This paper also r...

متن کامل

Characterization of Power Transformer Electromagnetic Forces Affected by Winding Faults

Electromagnetic forces in power transformer windings are produced by interaction between the leakage fluxes and current passing them. Since the leakage flux distribution along the windings height is in two axial and radial directions, so the electromagnetic forces have two components, radial and axial. There is a risk that a large electromagnetic force due to the short circuit or inrush current...

متن کامل

Neural Network Modeling of Distribution Transformer with Internal Winding Faults using Double Fourier Series

An efficient transformer model is required to characterize the transformer internal faults for its condition assessment, which is experimentally very costly. This paper discusses the application of Neural Network (NN) techniques in the modeling of a distribution transformer with internal short-circuit winding faults. A transformer model can be viewed as a functional approximator constructing an...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2001